Download Print deze pagina

MSA ULTIMA X5000 Gebruiksaanwijzing pagina 5

Verberg thumbnails Zie ook voor ULTIMA X5000:

Advertenties

DE VLAMBESTENDIGE VERBINDINGEN MOGEN NIET WORDEN GEREPAREERD.
GEBRUIK KABEL MET ISOLATIE GESCHIKT VOOR MINIMAAL 85 °C.
BIJ INSTALLATIE VAN DE ULTIMA X5000-TRANSMITTER MET RELAISOPTIE IN EEN ZONE 2 OF
ZONE 2 GECLASSIFICEERDE RUIMTE, MOET DE INSTALLATIE WORDEN UITGEVOERD MET
BEDRADING IN OVEREENSTEMMING MET ZONE 1/EXPLOSIEVEILIG OF ZONE 1/
EXPLOSIEVEILIG, ZOALS VAN TOEPASSING.
DE ULTIMA XIR PLUS INFRAROOD (IR)-SENSOR IS VOORZIEN VAN ¾" NPT SCHROEFDRAAD EN
MAG ALLEEN WORDEN AANGESLOTEN OP EEN ADEQUAAT GECERTIFICEERDE AFTAKDOOS
OF ADEQUAAT GECERTIFICEERD INSTRUMENT VOOR DE GEVAARLIJKE OMGEVING VAN DE
INSTALLATIE EN BIEDT DAARDOOR EX-BESCHERMING VOOR DE AANSLUITINGEN VAN DE
VOEDINGSKABEL. DE INSTALLATIE OP DE GECERTIFICEERDE BEHUIZING MOET GEBEUREN
MET VIJF MET EEN MOERSLEUTEL VOLLEDIG VASTGEDRAAIDE SCHROEFDRADEN.
DE ULTIMA XIR PLUS INFRAROOD (IR)-SENSOR MAG ALLEEN WORDEN GEMONTEERD OP
BEHUIZINGEN MET EEN MAXIMALE REFERENTIEDRUK VAN 13,5 BAR.
BIJ TOEPASSINGEN OM BRANDBARE GASSEN TE DETECTEREN, MAG HET GESCHIKTE ULTIMA
XIR PLUS-MODELNUMMER ALLEEN WORDEN GEBRUIKT OM HET VASTE
GASDETECTIESYSTEEM ULTIMA X5000 GASMONITOR TE CONSTRUEREN, GEMONTEERD OP
DE BEHUIZING VAN OFWEL DE ULTIMA X5000-TRANSMITTER OFWEL DE JB5000-
AANSLUITKAST MET VOEDING EN BEDIENING VANAF DE TRANSMITTER.
DE CLASSIFICATIE INDRINGINGSBESCHERMING IS UITSLUITEND GEBASEERD OP DE
INSTALLATIE-INSTRUCTIE VOOR DE ORIËNTATIE DIE IN DE GEBRUIKSAANWIJZING IS
GESPECIFICEERD.
DE ULTIMA XIR PLUS MAG ALLEEN WORDEN GEÏNSTALLEERD VOOR EXTERNE AANSLUITING
OP GESCHIKTE GECERTIFICEERDE APPARATUUR (TRANSMITTERS) MET BESCHERMING
TEGEN STROOMSTOTEN OP EEN MAXIMALE OVERSPANNING VAN 119 V (140% VAN DE 85V-
PIEK). DE GEBRUIKSAANWIJZING MOET DEZE INSTALLATIE-EIS VERSTERKEN.
WANNEER DE FABRIKANT VAN DE APPARATUUR HET TYPE BESCHERMING NIET OP HET
ETIKET HEEFT VERMELD, MOET DE GEBRUIKER BIJ DE INSTALLATIE OP HET ETIKET HET
GEBRUIKTE TYPE BESCHERMING AANGEVEN. WANNEER HET TYPE BESCHERMING EENMAAL
IS AANGEGEVEN, MAG DAT NIET MEER WORDEN GEWIJZIGD.
DE XIR PLUS-SENSORBEHUIZING MET SENSORBESCHERMING (ONDOORZICHTIGE
AFDEKKING) OF DE BEHUIZING MOET DE OPTISCHE STRALING VOLLEDIG INSLUITEN EN
VOLDOEN AAN EEN GESCHIKT TYPE BESCHERMING ZOALS VEREIST DOOR HET BETROKKEN
EPL, DAT AAN EEN VAN DE VOLGENDE VOORWAARDEN VOLDOET:
- EEN BEHUIZING WAARVOOR BESCHERMING INZAKE DE BINNENDRINGEN VAN EEN
EXPLOSIEVE STOFATMOSFEER IS VOORZIEN, ZOALS "t"-BEHUIZINGEN VOOR
STOFBESCHERMING (IEC 60079-31)
- EEN BEHUIZING DIE EEN MINIMALE BESCHERMING TEGEN BINNENDRINGING VAN IP 6X
BIEDT EN WAAR GEEN INTERNE ABSORBERS TE VERWACHTEN ZIJN EN DIE VOLDOET AAN
"TESTS VAN BEHUIZINGEN" IN IEC 60079-0
RICHTSNOEREN VOOR DE FUNCTIONELE VEILIGHEID VAN VASTE GASDETECTIESYSTEMEN
STAAN IN EN 60079-29-3, DIE NIET BINNEN HET BESTEK VAN DEZE BEOORDELING VALLEN.
EINDGEBRUIKERS ADVISEREN WIJ DE RICHTSNOEREN VAN EN 60079-29-2 TE RAADPLEGEN
VOOR INSTALLATIE, GEBRUIK EN ONDERHOUD VAN GASDETECTOREN VOOR BRANDBARE
GASSEN EN ANDERE TOEPASSELIJKE GASSEN.
Bijlage bij ULTIMA®X5000-gebruiksaanwijzing 10177361
PRESTATIES