NOTE! All safety-related parameters must be configured as follows in order to comply with the
appointed safety requirements:
 
The system must be configured in continuous radio mode
n
 
All relays must be switched off when the radio link is down
n
 
The radio link timeout must be set to a maximum of 500 ms
n
 
The login/logout function must be activated
n
 
The Custom ID setting must be deactivated, i.e. the receiver must always use the unique
n
transmitter ID code

INTERFACE

The radio system comprises one SRP/CS (as defined in EN 13849-1:2008), including the stop button
(input), the stop relays (output) and the saety-related logic maintening the stop function (logic).
The interfaces to the SRP/CS are the stop button (as controlled by the operator) and the stop relays.
INPUT
Transmitter's stop button
¢: Interconnection
R5
R5
R5
R5
R1
R2
R3
R4
 
LOGIC
¢
Safety-related logic
- 7 -
2
1. Stop relays
2. PLd status LED
 
OUTPUT
¢
Receiver's stop relays