EN
WARNING
Definition of warning signs:
Indication that a risk of electrical origin exists.
Indication that a risk exists for the machine or its operation.
Directions to be used only by qualified professionals.
Disconnect electrical power before working on the unit!
AREA OF APPLICATION
1
Sanicondens® Best Flat is a pump used to lift condensation water from an air conditioning system, a condensation
boiler, dehumidifiers or from refrigeration units. The unit has its own neutralisation system that can be used to
increase the pH of the acid water from the condensing boiler.
The pump starts automatically and has a high level of performance, safety and reliability as long as all the installation
and maintenance instructions mentioned in this manual are strictly followed.
All applications other than those described in this manual are prohibited.
DESCRIPTION
2
2.1 OPERATING PRINCIPLE
Sanicondens® Best Flat contains a pump. The tank of the Sanicondens® Best Flat has a built-in a float which
controls the operation of the motor. When the condensate enters the tank, the pump starts up.
Sanicondens® Best Flat has also a built-in secondary float that can trigger an alarm (audible and/or visual) and a
condensate neutralization system.
2.2 TECHNICAL DATA
Type
Max. vertical pumping
Maximum flow rate
Min. pH
Level ON/OFF
Voltage
Frequency
Current consumption
Power rating
Electrical class
Protection index
2.3 LIST OF PARTS SUPPLIED see pg. 6.
2.4 DIMENSIONS see pg. 11.
2.5 PERFORMANCE CURVES see pg. 11.
2.6 VERTICAL PUMPING/HORIZONTAL PUMPING see pg. 11.
START UP
3
3.1 INSTALLATION
Always install the pump: - horizontally, using a leveling tool,
To ensure proper ventilation of the motor, the pump must be free of any obstruction.
The pump can be mounted against a wall using the wall bracket C provided:
- Fix the wall bracket C horizontally with the plastic anchors A and screws B supplied (accessory bag). See fig. 1 and 2 .
- Snap the Sanicondens® Best Flat onto the bracket: fig. 3A and 3B .
- Check that the Sanicondens® Best Flat is leveled: fig. 3C .
3.2 HYDRAULIC CONNECTION
Connecting the inlet
The pump has two inlets that can be used as required:
- The upper inlet is open. If the upper inlet is used (fig. 5 ), close the lower side inlet with the supplied gasket F , cover
G and plug E (fig 4.2 ).
- To use the lower side inlet (fig. 4.1 ), place the plug E and Ø 32 mm gasket F on the inlet pipe and screw it onto the
inlet.
Drain the condensate water to any of these inlets. If necessary, use a rubber flexible adapter D .
CD 10
Sound level
4.5 m
Average operating temperature
380 L/h
Maximum allowable temperature
2.5
56 mm / 46 mm
Weight of the unit
220-240 V
Tank volume
50 Hz
Supply cable
0.52 A
Discharge hose
60 W
Alarm cable (2 cores)
Max. power for the connected
I
boiler
IP20
Wall mounting
- as close as possible to the appliance keeping in mind that the condensate has to
drain through gravity into the pump.
14
< 45 dBA
35°C
80°C
S3 15% (1min30 ON/8min30 OFF)
2 kg
3.5 L
1.5 m
5 m, Øint: 10mm
1.5 m
gas: 80 kW / oil: 50 kW
Yes