Download Inhoudsopgave Inhoud Print deze pagina

Nidec Control Techniques Unidrive M200 Handleiding pagina 178

Voor industriele automatisering met geintegreerde plc
Verberg thumbnails Zie ook voor Control Techniques Unidrive M200:
Inhoudsopgave

Advertenties

Trip
Nr.
SL.Er
202
Trip in optiemodule
Sub-
trip
200
SW fault
201
BG Orun
202
FW invalid
203
Drv unknown
204
Drv unsupported
205
Mode unknown
206
Mode unsupported
207
FLASH corrupt
208
Dbase init
209
FS init
210
Memory alloc
211
Filesystem
212
Configuration
213
OHt
214
TO drv
215
eCMP
216
TO eCMP slot 1
220
Output overload
Sub-
trip
100
No trip
101
Link loss
102
Invalid data
103
VPC3 stack
>200 Trip codes >200 raadpleeg de SI-PROFIBUS handleiding
Sub-
trip
100
Link Loss
101
INIT Switch
102
INIT TCP/IP
103
INIT Profinet
104
Profinet Start
105
Profinet Plug
106
Invalid M
107
CPM watchdog
108
Ethernet failure
>200 Trip codes >200 raadpleeg de SI-PROFINET handleiding
Sub-
trip
100
Link Loss
101
E/IP timeout
102
E/IP Read Param
103
E/IP Write Param
104
E/IP Fault
105
Modbus Timeout
106
Cyclic Timeout
107
Cyclic Rx Late
108
INIT Switch
109
INIT PTP
110
INIT Cyclic
111
INIT Modbus
112
INIT SMTP
113
INIT Ethernet/IP
114
INIT TCP/IP
115
Ethernet failure
116
E/IP PLC IDLE
117
Sync Task ORun
118
INIT Param Chann
119
Link Overload
120
Mcast Over Limit
>200 Trip codes >200 raadpleeg de SI-Ethernet handleiding
Sub-
trip
Invalid Fdbk Scr
ECAT Int Error
TO ECAT PDO
Sync Task Orun
M200 handleiding versie 5.3
M200
Error code's
Beschrijving
SI-I/O moduulcode 209 (#15.001 = 209)
Text string
SI-PROFIBUS moduulcode 443 (#15.001 = 443)
Text string
SI-PROFINET moduulcode 444 (#15.001 = 444)
Text string
SI-Ethernet moduulcode 433 (#15.001 = 433)
Text string
SI-EtherCAT moduulcode 431 (#15.001 = 431)
Text string
Pagina 178 van 186
Bijzonderheden
Tripnummer of text string wordt in display weergegeven.
Beschrijving
Software fault
Background task overrun
Invalid firmware for hardware version
Unknown drive type
Unsupported drive type
Unknown mode
Unsupported mode
Corrupted Non-volatile Flash
Database initialization error
File system initialization error
Memory allocation error
File system error
Configuration file error
Overheated
The drive has not responded with the watchdog period
eCMP comms failure
Slot 1 eCMP timeout
Digital output overload
Beschrijving
No trip
Network link lost
Invalid fieldbus specific data
VPC3 stack error
Beschrijving
Network link has been lost
Ethernet switch initialization error
TCP/IP initialization error
PROFINET initialization error
PROFINET start error
PROFINET plug error
Invalid IM data, EEPROM corrupted
Cyclic frame time out
Ethernet controller initialization error
Beschrijving
Network link has been lost
An Ethernet/IP RPI timeout trip has occurred
Invalid read consistency parameter, is read only?
Invalid write consistency parameter, is read only?
An unexpected Ethernet/IP error has occurred
The Modbus connection has timed out
Cyclic Rx link timeout
Cyclic Rx data was received late
Ethernet switch initialization error
IEEE1588 (Precision Time Protocol) initialization error
Cyclic data initialization error
Modbus TCP initialization error
Email (SMTP) initialization error
Ethernet/IP initialization error
TCP/IP initialization error
Ethernet controller initialization error
Ethernet/IP PLC Idle
Synchronous task overrun
Parameter channel initialization error
Too many links to be handled in the same cycle
Too many multicast addressing being used
Beschrijving
Unknown or invalid feedback source has been configured
Error while initializing the EtherCAT communications
A PDO not been written for longer than specified timeout
The synchronous task has overrun its allowed interval

Advertenties

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

Control techniques unidrive m201

Inhoudsopgave