Set Baud Rate
Parameter
Request:
Set Baud Rate
Response:
Set Baud Rate
Voorbeeld: U01B9600E71
Apparaat op adres 1 veranderen naar Baudrate 9600, pariteit even, 7 databits, 1 stopbit
Set Receive to Transmit Delay
Parameter
Request:
Set Receive to Transmit
Delay
Response:
Set Receive to Transmit
Delay
Report Number of Floats
Parameter
Request:
Report Number of Floats
Response:
Report Number of Floats
Report Receive to Transmit Delay
Parameter
Request:
Report Receive to Transmit
Delay
Response:
Report Receive to Transmit
Delay
Storingscodes
Error Code
EE-Error
FR-Error
LV-Error
VEGAFLEX 86 • Modbus- en Levelmaster-protocol
Length
8 (12) characters ASCII
11 characters ASCII
Length
7 characters ASCII
6 characters ASCII
Length
4 characters ASCII
5 characters ASCII
Length
4 characters ASCII
7 characters ASCII
Name
Error While Storing Data in EEPROM
Erorr in Frame (too short, too long, wrong data)
Value out of limits
Code/Data
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit (optional)
parity: none = N, even = E (default), odd = O
Code/Data
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
UuuROK
Code/Data
UuuF
UuuFn
n = number of measurement values
(0, 1 or 2)
Code/Data
UuuR
UuuRmmm
mmm = milliseconds (50 up to
250), default = 127 ms
11 Bijlage
91