THERMOSTAAT VRAAGT
OM WARMTE
DRUKSCHAKELAAR
OPEN?
YES
AFVOERVENTILATOR
GEACTIVEERD
YES
DRUK
SCHAKELAAR GESLOTEN?
YES
AFVOERVENTILATOR GEDURENDE 15 SECON-
DEN IN BEDRIJF
VOOR AFTAPPEN
YES
GASKLEP EN ONTSTEKER
ZIJN GEACTIVEERD
YES
VLAM
AANWEZIG?
AFVOERVENTILATOR GEDURENDE 15 SECON-
DEN IN BEDRIJF
VOOR AFTAPPEN
YES
30 SECONDEN OPWARMPERIODE
WARMTEWISSELAAR
YES
WARMTEVRAAG VOLDOENDE
GASKLEP SLUIT.
AFVOERVENTILATOR SCHAKELT NA 29
SECONDEN UIT.
INTERNE VENTILATOR SCHAKELT
NA INGESTELDE UITSCHAKELTIJD UIT.
30
PROBLEEMOPLOSSING
NO
NO
NO
www.goodmanmfg.com
3 FLITSEN - ONBEPERKTE
AFSLUITING TOTDAT
DRUKSCHAKELAAR OPENT
2 FLITSEN - VENTILATOR
BLIJFT IN BEDRIJF TOTDAT
DRUKSCHAKELAAR SLUIT.
TUSSENTIJDS AFTAPPEN
VAN START
IO-GMS9-DU