INSTALLATION
Installation

3.2.2 Heat pump manager settings

Appliance damage
!
f First set parameter "SOURCE" to ETHYLENE GLY-
f
COL and then set parameter "SOURCE MIN" to
2 °C on heat pump manager WPM II.
If the heat pump has an integral heat pump manager, observe
the following information.
Appliance damage
!
f For a brine/water heat pump with integral heat
f
pump manager, set parameter "SOURCE" to
"GWS".

3.2.3 Brine pressure switch DWS

To prevent any leaks causing damage to the heat pump, install
a brine pressure switch if not already pre-fitted to the brine/
water heat pump.
f Make the brine pressure switch electrical connections ac-
f
cording to the wiring diagram in chapter "Specification".
You can obtain a suitable brine pressure switch via your con-
tractor or from us as an accessory. For the part number, see
chapter "Accessories".

3.2.4 Fitting the push-fit connector

Push-fit connectors are fitted to the brine circuit connections
to make it easier to connect to the heat pump.
The push-fit connectors are equipped with a retainer with
stainless steel serrations and an O-ring for sealing. In addition,
they are designed with the "twist and lock" function. By sim-
ply turning the screw cap manually, the pipe is secured in the
connector, and the O-ring is pushed against the pipe to seal it.
Appliance damage
!
Support sleeves are required when using plastic pipes.
Making the connection
The connector must be in its relaxed position before the pipe
is inserted. In this position, there is a small gap between the
screw cap and connector body.
1
1 Gap between screw cap and connector body
f Always use a pipe cutter to trim the pipe.
f
f Push the deburred pipe past the O-ring into the connec-
f
tor as far as it will go.
f Tighten the screw cap fully to the casing. This presses the
f
O-ring against the pipe and locks the connector.
20 |
All manuals and user guides at all-guides.com
Pipe Ø
Depth of insertion A
Releasing the connection
f Undo the screw cap until a small gap appears.
f
f Press the retainer back with your fingers and hold on to it.
f

3.3 Installing the heat source system

Size the heat source circuit pump (well pump) for the heat
source system according to the system-specific conditions
(see chapter "Specification / Sizing table").
f Install a non-return valve above the source circuit pump.
f
f Fill the heat source system. Make sure there are no leaks.
f
28 mm
44 mm
The pipe can now be pulled out again.
Appliance damage
!
The groundwater temperature differential between
the heat source flow and return must be ≤ 3 K.
Note
The heat exchanger should only be operated in coun-
tercurrent (see chapter "Specification / Standard cir-
cuits").