Programmeren

Setupwizard voor toepassingen zonder terugkoppeling

Parameter
2
2
Parameter 0-03 Regionale instel-
lingen
Parameter 0-06 Type net
Parameter 1-10 Motorcon-
structie
12
®
VLT
HVAC Basic Drive FC 101
Optie
Standaard
[0] International (Interna-
[0] Internationaal
tionaal)
[1] US (VS)
[0] 200–240 V/50 Hz/IT-
Afhankelijk van
grid
grootte
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT-
grid
[11] 380–440 V/50 Hz/
Delta
[12] 380–440 V/50 Hz
[20] 440–480 V/50 Hz/IT-
grid
[21] 440–480 V/50 Hz/
Delta
[22] 440–480 V/50 Hz
[30] 525–600 V/50 Hz/IT-
grid
[31] 525–600 V/50 Hz/
Delta
[32] 525–600 V/50 Hz
[100] 200–240 V/60 Hz/IT-
grid
[101] 200–240 V/60 Hz/
Delta
[102] 200–240 V/60 Hz
[110] 380–440 V/60 Hz/IT-
grid
[111] 380–440 V/60 Hz/
Delta
[112] 380–440 V/60 Hz
[120] 440–480 V/60 Hz/IT-
grid
[121] 440–480 V/60 Hz/
Delta
[122] 440–480 V/60 Hz
[130] 525–600 V/60 Hz/IT-
grid
[131] 525–600 V/60 Hz/
Delta
[132] 525–600 V/60 Hz
*[0] Asynchron
[0] Asynchron
(Asynchroon)
(Asynchroon)
[1] PM, non-salient SPM
(PM, niet-uitspringende
SPM)
[3] PM, salient IPM (PM,
uitspringende IPM)
Danfoss A/S © 05/2018 Alle rechten voorbehouden.
Gebruik
Selecteer de bedieningsmodus die bij het starten actief
moet zijn wanneer de frequentieregelaar na een uitscha-
keling weer wordt aangesloten op de netvoeding.
Door het instellen van deze parameter kan de instelling
van de volgende parameters wijzigen:
Parameter 1-01 Motorbesturingsprincipe.
Parameter 1-03 Koppelkarakteristiek.
Parameter 1-08 Motor Control Bandwidth (Bandbreedte
motorregeling).