5.1.15 20-** Drive Closed Loop (Frequentieregelaar met terugkoppeling)

Para
Parameter description
meter
num
ber
20-0* Feedback
20-00
Feedback 1 Source
20-01
Feedback 1 Conversion
20-03
Feedback 2 Source
20-04
Feedback 2 Conversion
5
5
20-12
Reference/Feedback Unit
20-2* Feedback/Setpoint
20-20
Feedback Function
20-21
Setpoint 1
20-6* Sensorless
20-60
Sensorless Unit
20-69
Sensorless Information
20-7* PI Autotuning
20-70
Closed Loop Type
20-71
PI Performance
20-72
PI Output Change
20-73
Minimum Feedback Level
20-74
Maximum Feedback Level
20-79
PI Autotuning
20-8* PI Basic Settings
20-81
PI Normal/ Inverse Control
20-83
PI Start Speed [Hz]
20-84
On Reference Bandwidth
20-9* PI Controller
20-91
PI Anti Windup
20-93
PI Proportional Gain
20-94
PI Integral Time
20-97
PI Feed Forward Factor

5.1.16 22-** Appl. Functions (Toepassingsfuncties)

Para
Parameter description
meter
num
ber
22-0* Miscellaneous
22-01
Power Filter Time
22-02
Sleepmode CL Control Mode
22-2* No-Flow Detection
22-23
No-Flow Function
22-24
No-Flow Delay
22-3* No-Flow Power Tuning
22-30
No-Flow Power
22-31
Power Correction Factor
22-33
Low Speed [Hz]
22-34
Low Speed Power [kW]
128
®
VLT
HVAC Basic Drive FC 101
Default value
4 set-up
[0] No function
All set-ups
[0] Linear
All set-ups
[0] No function
All set-ups
[0] Linear
All set-ups
ExpressionLimit
All set-ups
[3] Minimum
All set-ups
0 ProcessCtrlUnit
All set-ups
ExpressionLimit
All set-ups
0 N/A
[0] Auto
[0] Normal
0.10 N/A
-4999.000
ProcessCtrlUnit
4999.000
ProcessCtrlUnit
[0] Disabled
[0] Normal
All set-ups
0 Hz
All set-ups
5 %
All set-ups
[1] On
All set-ups
0.50 N/A
All set-ups
20 s
All set-ups
0 %
All set-ups
Default value
4 set-up
0.50 s
2 set-ups
ExpressionLimit
All set-ups
[0] Off
All set-ups
10 s
All set-ups
0 kW
All set-ups
100 %
All set-ups
0 Hz
All set-ups
0 kW
All set-ups
Danfoss A/S © 05/2018 Alle rechten voorbehouden.
Change during
operation
TRUE
TRUE
TRUE
FALSE
TRUE
TRUE
TRUE
TRUE
1 set-up
TRUE
1 set-up
TRUE
1 set-up
TRUE
1 set-up
TRUE
1 set-up
TRUE
1 set-up
TRUE
1 set-up
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
Change during
operation
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
Conversion
Type
index
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-3
Int32
-
Uint8
0
VisStr[25]
-
Uint8
-
Uint8
-2
Uint16
-3
Int32
-3
Int32
-
Uint8
-
Uint8
-1
Uint16
0
Uint8
-
Uint8
-2
Uint16
-2
Uint32
0
Uint16
Conversion
Type
index
-2
Uint16
-
Uint8
-
Uint8
0
Uint16
1
Uint32
0
Uint16
-1
Uint16
1
Uint32
MG18B510