Different options for installation
Remember to always follow instructions and recommendations for installation.
To prevent the outgoing air from coming back into the space where the toilet is placed, the distan-
ce between the air intake (fresh air valve) and the ventilation outlet (ventilation cowl) should be at
the minimum 3-4 meters. If the distance between intake air and ventilation outlet is less than 3-4
meters, the condensation hose in the 90 degree bend should be fitted before use. We recom-
mend one of the following three options for installation.
Option 1
Internal installation through the roof.
A. Use the connecting pipe (100 mm) between the toilet and the 90 degree bend
B. Total lenght from the 90 degree bend - maximum 5 meters
C. Maximum 500 mm above the roof
D. Attach the supplied hose on the drain tap on the 90 degree bend to divert condensation
Fresh air vent is placed on an outer wall, min Ø 125 mm.
NOTE! Only Ø 110 mm ventilation pipe made of plastic, two 45 degree bend and one 90 degree bend
may be used in the installation. When installing a 90 degree bend tube directly behind the toilet, 30 cm
space is required for installation behind the toilet.
C
B
A
D
Do not forget to install the
condensation hose.
EN-14