dixell XC1008D Handleiding pagina 27

Electronische stappenregelaar voor centrales
Inhoudsopgave

Advertenties

F
Nome
XC
XC
XC
Level Description
1008 D
1011 D
1015 D
F5
-
4.0
4.0
Pr1
Regulation band width circuit 2
F6
-
10.0
10.0
Pr1
Minimum set point circuit 2
F7
-
60.0
60.0
Pr1
Maximum set point circuit 2
F8
-
0.0
0.0
Pr1
Energy saving circuit 2
F9
15
15
15
Pr1
2 different fan start delay
F10
5
5
5
Pr1
2 different fan off delay
HS1
nu
nu
nu
Pr1
Energy Saving start time on Monday
HS2
00,00
00:00
00:00
Pr1
Monday Energy Saving duration
HS3
nu
nu
nu
Pr1
Energy Saving start time on Tuesday
HS4
00,00
00:00
00:00
Pr1
Tuesday Energy Saving duration
HS5
nu
nu
nu
Pr1
Energy Saving start time on Wednesday 0:0÷23.5h; nu
HS6
00,00
00:00
00:00
Pr1
Wednesday Energy Saving duration
HS7
nu
nu
nu
Pr1
Energy Saving start time on Thursday
HS8
00,00
00:00
00:00
Pr1
Thursday Energy Saving duration
HS9
nu
nu
nu
Pr1
Energy Saving start time on Friday
HS10
00,00
00:00
00:00
Pr1
Friday Energy Saving duration
HS11
nu
nu
nu
Pr1
Energy Saving start time on Saturday
HS12
00,00
00:00
00:00
Pr1
Saturday Energy Saving duration
HS13
nu
nu
nu
Pr1
Energy Saving start time on Sunday
HS14
00,00
00:00
00:00
Pr1
Sunday Energy Saving duration
AC1
30
30
30
Pr1
Probe 1 alarm delay at power on
AC2
-
30
30
Pr1
Probe 2 alarm delay at power on
AC3
15,0
15.0
15.0
Pr1
Minimum temp/press alarm circuit 1
AC4
20,0
20.0
20.0
Pr1
Maximum temp/press alarm circuit 1
AC5
20
20
20
Pr1
Temp/press alarm delay circuit 1
AC6
-
15.0
15.0
Pr1
Minimum temp/press alarm circuit 2
AC7
-
20.0
20.0
Pr1
Maximum temp/press alarm circuit 2
AC8
-
20
20
Pr1
Temp/press alarm delay circuit 2
AC9
ALr
ALr
ALr
Pr1
Relay for temp/press alarm
AC10
20000
20000
20000
Pr1
Running hours for maintenance
AC11
ALr
ALr
ALr
Pr1
Relay for maintenance alarm
AC12
15
15
15
Pr1
LP switch 1 activation number
AC13
15
15
15
Pr1
LP switch 1 activation time
AC14
2
2
2
Pr1
Compressure on-faulty probe1
AC16
-
15
15
Pr1
LP switch 2 activation number
AC17
-
15
15
Pr1
LP switch 2 activation time
AC18
-
2
2
Pr1
Compressure on-faulty probe2
AF1
20,0
20.0
20.0
Pr1
Minimum temp/press alarm circuit 1
AF2
20,0
20.0
20.0
Pr1
Maximum temp/press alarm circuit 1
AF3
20
20
20
Pr1
Temp/press alarm delay circuit 1
AF4
no
NO
NO
Pr1
Compressor off with max alarm 1
AF5
2
2
2
Pr1
Off delay with max alarm 1
AF6
15
15
15
Pr1
HP switch 1 activation number
AF7
15
15
15
Pr1
HP switch 1 activation time
AF8
2
2
2
Pr1
Fans on with faulty probe 3
XC1015D_V15.doc
Handleiding
Range
(BAR)
0.10÷10.00
(°C)
0.0÷30.0
(PSI)
1÷80
(°F)
1÷50.0
BAR: (AI12 ÷ SETF2); °C: (-50.0 ÷ SETF2); PSI
: (AI12 ÷ SETF2); °F : (-58.0 ÷ SETF2)
BAR: (SETF2÷AI13); °C : (SETF2 ÷ 150.0); PSI :
(SETF2 ÷ AI13); °F: (SETF2 ÷ 302)
(BAR)
(°C)
(PSI)
-20.00÷20.00
-50.0÷50.0
-300÷300
(°F)
-90÷90
1 ÷ 255 (sec)
1 ÷ 255 (sec)
0:0÷23.5h; nu
0:0÷23.5h;
0:0÷23.5h; nu
0:0÷23.5h;
0:0÷23.5h;
0:0÷23.5h; nu
0:0÷23.5h;
0:0÷23.5h; nu
0:0÷23.5h;
0:0÷23.5h; nu
0:0÷23.5h;
0:0÷23.5h; nu
0:0÷23.5h;
0 ÷ 255 (min)
0 ÷ 255 (min)
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
°F
(1 ÷ 200.0)
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
(1 ÷ 200.0)
°F
0 ÷ 255 (min)
BAR
°C
PSI
(0.10 ÷ 30.00)
(0.0 ÷ 100.0)
(1 ÷ 430)
°F
(1 ÷ 200.0)
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
°F
(1 ÷ 200.0)
0 ÷ 255 (min)
nu - ALr - ALr1 - ALr2
0 ÷ 25000 – with 0 the function is disabled
nu - ALr - ALr1 - ALr2
0 ÷ 15
0 ÷ 255 (min)
0 ÷ 15
0 ÷ 15
0 ÷ 255 (min)
0 ÷ 15
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
(1 ÷ 200.0)
°F
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
(1 ÷ 200.0)
°F
0 ÷ 255 (min)
no - YES
0 ÷ 255 (min)
0 ÷15
0 ÷ 255 (min)
0 ÷ 15
rel. 1.5 (11.12.11)
Nome
XC
XC
XC
Level Description
1008 D
1011 D
1015 D
AF9
-
20.0
20.0
Pr1
Minimum temp/press alarm circuit 2
AF10
-
20.0
20.0
Pr1
Maximum temp/press alarm circuit 2
AF11
-
20
20
Pr1
Temp/press alarm delay circuit 2
AF12
-
NO
NO
Pr1
Compressor off with max alarm 2
AF13
-
2
2
Pr1
Off delay with max alarm 2
AF14
-
15
15
Pr1
HP switch 2 activation number
AF15
-
15
15
Pr1
HP switch 2 activation time
AF16
-
2
2
Pr1
Fans on with faulty probe 3
AF17
ALr
ALr
ALr
Pr1
Relay for temp/press alarm
O1
no
NO
NO
Pr2
Dynamic set enabled - circuit 1
O2
-18,0
-18.0
-18.0
Pr2
Maximum set for circuit 1
O3
15,0
15.0
15.0
Pr2
Dynamic set start temperature circuit 1
O4
15,0
15.0
15.0
Pr2
Dynamic set stop temperature circuit 1
O5
-
NO
NO
Pr2
Dynamic set enabled - circuit 2
O6
-
-18.0
-18.0
Pr2
Maximum set for circuit 2
O7
-
15.0
15.0
Pr2
Dynamic set start temperature circuit 2
O8
-
15.0
15.0
Pr2
Dynamic set stop temperature circuit 2
O9
no
NO
NO
Pr2
Dynamic set enabled - circuit 1
O10
25,0
25.0
25.0
Pr2
Minimum condens. set - circuit 1
O11
15
15.0
15.0
Pr2
Differential dynamic set-circuit 1
O12
-
NO
NO
Pr2
Dynamic set enabled - circuit 2
O13
-
25.0
25.0
Pr2
Minimum condens. set - circuit 2
O14
-
15.0
15.0
Pr2
Differential dynamic set-circuit 2
1Q1
4.20mA 4.20mA 4.20mA
Pr1
Analog outputs 1-2 setting
1Q2
nu
nu
nu
Pr1
Analog output 1 function
1Q3
Pbc1
Pbc1
Pbc1
Pr1
Probe for analog output 1
1Q4
0.0
0.0
0.0
Pr1
Lower limit for analog output 1
1Q5
100.0
100.0
100.0
Pr1
Upper limit for analog output 1
1Q6
30
50
50
Pr1
Minimum value for analog output 1
1Q7
40
50
50
Pr1
Analog output 1 value after compressor
start
1Q8
40
60
60
Pr1
Analog output 1 value after compressor
off
1Q9
40
50
50
Pr1
Exclusion band start value 1
1Q10
40
50
50
Pr1
Exclusion band end value 1
1Q11
50
50
50
Pr1
Safety value for Analog output 1
1Q12
0
0
0
Pr1
Regulation delay after exit from neutral
zone
1Q13
150
120
120
Pr1
Analog output 1 rise time
1Q14
10
10
10
Pr1
Analog output 1 permanency before load
activation
1Q15
0
2
2
Pr1
Analog output 1 decreasing delay
1Q16
150
5
5
Pr1
Analog output 1 decreasing time
1Q17
10
5
5
Pr1
Analog output 1 permanency before load
off
1Q18
5
5
5
Pr1
Analog output 1 decreasing time after
load off
1Q19
4.0
4.0
4.0
Pr1
Regulation band width 1
cod. 1592021021
Range
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
(1 ÷ 200.0)
°F
(0.10 ÷ 30.00)
BAR
(0.0 ÷ 100.0)
°C
(1 ÷ 430)
PSI
(1 ÷ 200.0)
°F
0 ÷ 255 (min)
no - YES
0 ÷ 255 (min)
0 ÷15
0 ÷ 255 (min)
0 ÷ 15
nu - ALr - ALr1 - ALr2
no - YES
SETC1÷CP3
-40÷O4 °C /-40÷O4°F
O3÷150°C /O3÷302°F
no - YES
SETC2÷CP7
-40÷O8°C /-40÷O8°F
O7÷150°C /O7÷302°F
no - YES
F2÷SETF1
(BAR) -20.00÷20.00 (°C) -50.0÷50.0 (PSI) -
300÷300 (°F) -90÷90
no - YES
F6÷SETF2
(BAR) -20.00÷20.00 (°C) -50.0÷50.0 (PSI) -
300÷300 (°F) -90÷90
4.20 mA (0) - 0.10 V (1)
FREE – CPR - CPR2 - FAN - FAN2 - INVF1 -
INVF2 - nu
Pbc1(0) - Pbc2(1) ; used only with 1Q2 = 0
-1÷100.00 bar; -15÷750PSI; -50÷150°C; -
58÷302°F;
-1÷100.00 bar; -15÷750PSI; -50÷150°C; -
58÷302°F;
0 ÷ 100 %
1Q6 ÷ 100 %
1Q6 ÷ 100 %
1Q7 ÷ 100 %
1Q9 ÷ 100 %
0 ÷ 100 (%)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0 ÷ 255 (sec)
0.10÷25.00bar; 0.0÷25.0°C; 1÷250 PSI;
1÷250°F;10÷2500 KPA
Page
27 / 29