It is possible to activate the sound alarm output (and also all the other alarm outputs described later) for 15 types of
alarms. One or more alarms can be activated as desired. To activate an alarm set the value from "0" to "1" in the
following table
1
Phase Seq., Min Hz, Max Hz
2
4-20 mA device malfunction
3
4
5
6
7
8
9
10
11
Max start per minute, Max start per hour
12
Max Klixon interventions
13
Detection of water in oil chamber
14
Max continous working
15
(only whit GSM modem) Absence/Return mains
16
(only whit GSM modem) Black-out Max level
17
(only whit GSM modem) Low battery
18
NOTE: the alarms in gray are automatically sent only if is mounted GSM modem.
There is no need any configuration and it's not possible to disable these features.
For example, the mask "100110000000000" will activate the following alarms: V Min, V Max, Min Level e Max Level.
The FULL-APP² always shows to display each alarm detected, but it will activate the alarm output only if it's configured
properly.
N.B.: The alarms "I Min, cos φ Min", "I max", "Service Request", "Max Starts per Minute/Hour",
"Intervention Klixon", "Water in Oil Chamber" e "Max Continuous Operation", TO BE ACTIVATED, MUST BE
ASSOCIATED TO AT LEAST ONE PUMP; THERE MUST BE ACTIVE AT LEAST ONE OF THE "ALARMS PUMP".
To go back to the horizontal menu press the button
Configuration
GSM Alarm
Press the button
to move to the configuration of the next alarm output :
Configuration
Sound Alarm
The vertical parameter "Configuration Sound Alarm" will set the operating mode of the visual
alarm output on GSM card (therefore, GSM option must be present). It is an output voltage 12
Vcc, max 30 mA) with faston connector (see page 41). This is set-up to be connected to a
Configuration
flashing alarm but it could be used for any other device with the following electrical
Visual Alarm
characteristics: 12 Vcc, 30 mA max.
Factory default setting: 100111111100110.
38
ALARM ON
1
1
1
ALARM OFF
0
0
0
V Min, V Max
Min level
Max level
Pump 1 alarms
Pump 2 alarms
Pump 3 alarms
I Min, cosφ Min
I max
Service
Configuration
Sound Alarm
Configuration
Visual Alarm
1
1
1
1
1
1
0
0
0
0
0
0
. Back to the horizontal menu "Configuration Sound Alarm":
Configuration
Visual Alarm
Configuration
Relay 1
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
not be disabled