While the maximum delivery temperature is limited by the value set on the unit, the lower threshold of the curves is
determined by the COOLING USER SETPOINT parameter (MENU >> SETTINGS >> TECHNICAL >> ZONES MAN-
AGER >> (CHOOSE THE DESIRED ZONE) >> CLIMATIC CURVES >> COOLING >> USER SETPOINT).
Note
If the USER SETPOINT value is lower than the minimum flow temperature set on the unit, then the
curves will be limited to this latter value.
Example: curves with "USER SETPOINT" set at 10 °C, min. flow temperature set on the unit at 5 °C, max. flow
temperature set on the unit 25 °C and offset of 20°C.
[ a ]
25
20
15
[ b ]
10
[ c ]
5
0
10
In addition to the climatic curve and the OFFSET, the CRP allows the setting of parameter K, which will affect modu-
lation of the flow temperature as a function of the room temperature:
if the room temperature is between the set point - 0.1 °C and the set point + 2 °C, the flow temperature set point will
be equal to
Cooling user setpoint – (K/10) * (T_amb - 2 -Tcomfort)
where T_amb is the room temperature and T_comfort is the desired temperature
PERMISSIBLE RANGES:
CLIMATIC CURVES
OFFSET
K
USER SETPOINT
NOTE: With climate control disabled, the flow temperature will always be controlled by the Connect CRP, for
optimum regulation.
20
30
40
A
fig. 90
0 – 10 (0 = Climatic not enabled)
20 °C – 40 °C
0 – 20
5 °C ÷ 25 °C
cod. 3542B390 - Rev 04 - 01/2023
[ a ] = Max. flow temperature set on the unit
[ b ] = USER SETPOINT
[ c ] = Min. flow temperature set on the unit
50