Download Print deze pagina

Lamborghini Caloreclima Connect CRP Handleiding Voor Installatie En Gebruik pagina 119

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 203
While the minimum flow temperature is limited by the value set on the unit, the upper threshold of the curves is deter-
mined by the HEATING USER SET POINT parameter (MENU >> SETTINGS >> TECHNICAL >> ZONES MANAGER
>> (CHOOSE THE DESIRED ZONE) >> CLIMATIC CURVES >> HEATING >> USER SETPOINT).
Note
If the USER SETPOINT value is greater than the maximum flow temperature set on the unit, then the
curves will be limited to this latter value.
Example: curves with "USER SETPOINT" set at 60 °C, max. flow temperature set on the unit at 65 °C, min. flow
temperature set on the unit of 25 °C and offset of 30 °C.
80
70
[ a ]
65
[ b ]
60
50
40
30
[ c ]
25
20
25
20
15
In addition to the climatic curve and the OFFSET, the CRP allows the setting of parameter K, which will affect modu-
lation of the flow temperature as a function of the room temperature:
if the room temperature is between the set point - 2 °C and the set point + 0.1 °C, the flow temperature set point will
be equal to
Heating user setpoint – K*(T_amb + 2 -Tcomfort)
where T_amb is the room temperature and T_comfort is the desired temperature
PERMISSIBLE RANGES:
CLIMATIC CURVES
OFFSET
K
USER SETPOINT
NOTA: Con la climatica non abilitata, la temperatura di mandata sarà sempre controllata dal Connect CRP,
per una regolazione ottimale.
10
5
0
-5
A
fig. 85
0 – 10 (0 = Climatic not enabled)
20 °C – 40 °C
0 – 20
25 °C ÷ 65 °C
cod. 3542B390 - Rev 04 - 01/2023
[ a ] = Max. flow temperature set on the unit
[ b ] = USER SETPOINT
[ c ] = Min. flow temperature set on the unit
-10
-15
-20
119
EN

Advertenties

loading

Gerelateerde Producten voor Lamborghini Caloreclima Connect CRP