6.2.1
CONNECT CRP TEMPERATURE SENSOR CALIBRATION
The Connect CRP allows the detected room temperature to be corrected by entering an offset between -6 °C and
+6 °C,
in steps of 0.1°C.
The default value is set to 0.0°C.
1. Access the "TECHNICAL" menu (see "6.1 Accessing the TECHNICAL menu" on page 111)
2. Follow the path "MENU >> TECHNICAL >> INSTALLATION >> SENSOR CALIBRATION"
3. Use the
and
ed by the Connect CRPwill be shown above the offset value .
4. Press the
button to confirm the entered value
6.3
TECHNICIAN MENU - SYSTEM TYPE
Using the
and
TYPE menu and confirm with the
From this menu it is possible to set the type of system that the Connect CRP will manage. The available settings are:
FULL ELECTRIC
Monobloc or split heat pump, with or without
storage tank and without the aid of a boiler as
support
HYBRID H
Hybrid system for room heating/cooling and
DHW production, consisting of heat pump and
boiler as support, with or without storage tank
6.4
TECHNICIAN MENU - DIGITAL INPUT
Using the
and
menu and confirm with the
From this menu it is possible to enable and disable the
"Digital inputs" function.
NOTE For correct configuration, the system config-
uration must be scrupulously followed.
NOTE When this function is active the system will
follow its own setpoint and will not be managed by
the Connect CRP (for a correct set point setting, re-
fer to the system manual).
NOTE With the digital inputs enabled, it will not be
possible to set the climatic curves.
buttons to change the offset of the detected temperature: the new temperature value detect-
buttons, select the SYSTEM
button .
buttons, select the "Digital inputs"
button.
cod. 3542B390 - Rev 04 - 01/2023
T E C H N I C A L
I N S T A L L A T I O N
S Y S T E M T Y P E
D I G I T A L I N P U T S
I N S T A L L E R
fig. 70
HYBRID C
Hybrid system for room heating/cooling, consist-
ing of heat pump and instantaneous boiler as
support. DHW production is only with boiler.
NOTE
For correct system setup, refer to the unit model.