5.2.2
Sludge separator with removable floor flange
The separator element at the equipment can be cleaned and replaced, if required.
–
The equipment must have cooled down, been emptied, and de-pressurised.
–
Keep a suitable flange gasket at hand.
For cleaning, proceed as follows:
1. Use appropriate lifting gear to carefully lower the separator element and the bottom cover to the floor.
–
Ensure that the separator element can neither topple nor roll away or execute other unintended movements.
–
Avoid damage to the draw-off tap.
2. Remove any deposits from the separator element.
–
Use a water jet or low-pressure cleaner.
Reassemble in reverse order.
3. Insert a functioning gasket.
4. Tighten the flange screws with a suitable torque.
–
Tighten diagonally and step-by-step as per the state of the art.
5.2.3
Sludge separator with magnet insert
Caution – magnetic field!
•
The device contains permanent magnets generating a static magnetic field. Magnets may affect the functioning of
cardiac pacemakers and implanted defibrillators.
–
Persons with such medical devices or other metallic implants must maintain sufficient distance to magnets.
–
Provide warning information before people enter the sphere of influence of magnets.
The device can be emptied without the operation being shut down.
For emptying, proceed as follows:
1. Unscrew the magnet from the immersion sleeve.
2. Provide a vessel to capture the drained material.
3. Slowly or for a short time only open the draw-off tap.
4. Screw the magnet into the immersion sleeve.