Operation
3.7
exdirt / extwin
Properly install the draw-off tap at the devices.
3.8
exvoid / extwin
Comply with the following instructions:
For a hydraulic pressure test at the equipment, install a blind cover (to be supplied by the user) at the blow-off opening of the
venting mechanism.
To drain the released air or gases (odour), you may connect an additional hose or pipe at the ½" thread of the blow-off opening.
4
Operation
Note the following for operation:
The glycol portion of the water must be maximal 50 percent.
When dosing additives, comply with the manufacturer specification regarding the permissible dosing quantities. This is important
in particular to prevent corrosion.
Chemical additives such as inhibitors must be used only after an impact assessment in respect to all the materials used in the
system.
This impact assessment is the responsibility of the user.
Keep the system free from foaming substances. Foam or dirt beyond a specific portion can cause a temporary leaking at the venting
valve.
5
Maintenance
Caution – risk of burning!
Excessive surface temperatures in heating systems can cause skin to burn.
Wait until surfaces have cooled down or wear protective gloves.
The operator is required to attach corresponding warning notes in the device vicinity.
The time intervals for maintenance work depend on the specific operating conditions.
5.1
Pressure test
During a hydraulic pressure test, the pressure must not exceed 1.5 times the maximum working pressure.
5.2
Cleaning
5.2.1
Sludge separator
The cleaning interval depends on the accumulated dirt within the system.
Provide a catching container and a pressure and temperature-resistant drain hose, if required.
For cleaning, proceed as follows:
1. Gradually open the desludging valve for a short time until sludge no longer drains off.
Make sure that not much water escapes.
2. Subsequently, check the system pressure and add water as required.