Installation and assembly
3.5
Notes
The following items must be considered when assembling and installing the equipment:
The flow direction is not pre-determined.
Ensure a vertical and stress-free installation.
Any stresses that may occur in some cases must be countered by appropriate constructive actions. Stresses may be caused by
temperature effects, for example.
Ensure sufficient bearing capability of the installation site.
This applies to filling the separator with water in particular.
The equipment is not a load-bearing construction element.
By default, the calculation of the vessels does not take lateral acceleration forces into account. Avoid alternating stresses such
as pressure shocks, abrupt pressure changes, or strong vibrations.
Use only approved transport and lifting gear.
The eyes provided on the device are intended solely as
installation aids.
The angle (1) of the lifting tackles must be maximum 60°.
3.6
Space requirements
A: Minimum free space above the top part of the ventilation
Type:
Type:
82511 xx
82531 xx
82513 xx
82532 xx
82533 xx
82534 xx
50 mm
50 mm
B: Minimum free space below the draw-off tap
Connection
Connection
DN 50 / 65
OD 60.3 / 76.1
DN 80 / 100
OD 88.9 / 114.3
DN 125 / 150 OD 139.7 / 168.3
DN 200
OD 219.1
DN 250
OD 273.0
DN 300
OD 323.9
ГК Водная техника info@water-technics.ru (495) 771 72 72 www.water-technics.ru
Интернет-магазин info@wtpump.ru (499) 937 50 61 (800) 505 78 67 www.wtpump.ru
Type:
Type:
82531 xx
82521 xx
82532 xx
82522 xx
82533 xx
82523 xx
82534 xx
82524 xx
400 mm
300 mm
550 mm
400 mm
750 mm
500 mm
1000 mm
700 mm
1350 mm
850 mm
1700 mm
1000 mm
Reflex ex separator — 27.01.2014
1
A
B
Technical data
60°
A
B
English — 9