Download Print deze pagina

Vasco ENERGY plus Installatie-, Gebruiks- En Onderhoudsvoorschriften pagina 152

Advertenties

Beschikbare talen

Beschikbare talen

English
ELECTRIC POST-HEATING
COIL BER
(to be placed on the "Intake air"
duct)
Electric heating coil consisting of armored
elements inserted inside a galvanised sheet
metal duct section with circular flanges and
rubber gasket. The electric coil can be used in
premises with air temperature between -20°
C and +40° C and is equipped with double
safety thermostat: one with automatic re-
set and one with manual reset. Operation
is driven by the control with ON/OFF logic
in order to track the heating setpoint of the
supply air, controlled via the temperature
probe located on the supply air flow, or of
the room air, controlled via the temperature
probe located on the return air flow.
In the case of supply air temperature control,
the PT 1000 sensor on the supply air inlet
must be repositioned so that it is located
downstream of the post-treatment element.
The PT 1000 sensor must be ordered sepa-
rately from the list of available accessories.
18
16
14
12
Duct fitted
by the installer
10
8
6
4
2
0
0
500
F
heat recovery uNIt
or
I
resIstaNce
deNtIFIcatIoN
Rated power
Power supply voltage
Amperes absorbed by the resistance
Circular Flange Diameter
Minimum air flow rate
18
16
14
12
10
8
6
1000
4
1500
2000
Supply air
2
0
0
500
ENY–P1
BER 25/2/M
c
9022114
ode
kW
2,1
V/Hz/Ph
A
9,1
D
mm
250
m
/h
270
3
The resistance supply circuit is
fitted with an adjustable thermostat, which
has a limiting function. Protection class IP 43.
18
16
14
12
10
8
6
4
2
0
0
2500
3000
1000
1500
2000
ENY–P2
BER 25/3/M
9022214
3,0
230V 50Hz 1Ph + Pe
13,0
250
300
152
Pressure drop BER
BER40/6
500
1000
1500
2000
BER35/5
Air flow rate (m
/h)
3
BER25/2
BER25/3
2500
3000
AIR
ENY–P3
BER 35/5/T
9022314
4,5
400V 50Hz 3Ph + Pe
7,2
355
600
2500
3000
BER40/6
BER35/5
BER25/2
BER25/3
ENY–P4
BER 40/6/T
9022414
6,0
8,7
400
690
BER4
BER3
BER2
BER2

Advertenties

loading