INVERTING THE AIR FLOWS
OF CEILING UNITS
In the case of ceiling units, the condensate tray
needs to be moved in order to invert the flows.
Typical Ceiling Installation
C
B
Inverted Air Flows of Ceiling Installation
B
C
This operation is simple and involves the remo-
val of the three lower panels and disassem-
bly of the condensate tray for reassembly
on the opposite side of the heat exchanger,
turning it through 180°.
The central panel has a pre-punched hole
which is to be opened for the condensate
drain fitting.
When not in use, the hole must be carefully
sealed with closed-cell insulation.
A
D
D
A
134
FOR INVERTING THE FLOW:
INVERT THE LOCATION OF THE CONDENSATE
AND THE POSITION OF DIP SWITCH 1
ON THE ELECTRONIC POWER BOARD
TYPICAL OPERATION
F7
FILTER
ELECTRONIC
BOARD
DIP 1 = OFF
INVERTING THE AIR FLOW OPERATION
F7
FILTER
ELECTRONIC
BOARD
DIP 1 = ON
TRAY
DIP 1 position
Condensate tray
FILTER
F7
Condensate tray
FILTER
F7