Outdoor unit

1
Remove the tubing cover from the unit by
loosening the screw.
• 2.5/3.5/5.0 kW
• 6.6 kW
2
Align the center of the pipings and
sufficiently tighten the flare nut by hand.
Connector
* When Indoor unit(5.0/6.6 kW) is connected
to the Multi Outdoor unit, use the connector
shown above.
3
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for
tightening follows the arrow on the
wrench.
Outdoor unit
Torque wrench
* The feature can be changed according a
type of model.
Outside Diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Gas side piping
(Bigger diameter)
Liquid side piping
(Smaller diameter)
Torque
kgf . cm
N . m
180~250 17.6~24.5
340~420 33.3~41.2
550~660 53.9~64.7
630~820 61.7~80.4