15. CONTROLS - OPTIONAL ELEMENTS
TS
3-step regulator with built-in thermostat
Temperature setting range: +10 ... +30
Operating temperature range: 0 ... +40
Protection degree: IP30
Contact load: inductive: 5 A
Supply voltage: 230 V/50 Hz
FAN AUTO - fan operation depends on the
temperature.
FAN CONT - continuous fan operation
HEAT - heating function
FAN - deactivate the thermostat for FAN CONT
COOL - reversal of the operation logic of the
thermostat
T-box + DRV Slim (BMS possibility)
T-box + DRV Slim - touch screen controller +
control system
T-box:
Temperature setting range: +5 ... + 35
temperature range: -10 ... + 60
C Protection degree:
o
IP30
Supply voltage: 24 VDC
DRV Slim:
Operating temperature range: -10 ... + 60
Protection degree: IP54
Supply voltage: 230 V / 50 Hz
CONNECTION DIAGRAM IS IN DRV SLIM
DOCUMENTATION
16. ADJUSTMENT OF OUTLET GRILLE
PIC. 16.1 MANUAL ADJUSTMENT OF OUTLET GRILLE.
C
o
C
o
15.1. SLIM E + TS .
❶❷❸ The connection diagram for the remaining elements, along with a description of the
cables and protections, can be found in sections 12 and 13.
❹
TS 3-step fan speed controller with thermostat TS (min. 5x1,0 mm
ADVICE
WARNING
ADVICE
C Operating
o
WARNING
o
C
15.2. SLIM W/N + TS.
The curtain is activated automatically when motion is detected in the sensor
area and works with the settings selected on the TS controller. In order to
the connectors: D D; - see ❸ Chapters 13 and 14
work only with the TS controller, a cable jumper should be made between
When connecting the TS controller to the air curtain, disconnect and isolate
the wires from air curtain connectors 1; 3; 6; 8. In this case, the built-in
switches are disconnected and not active.
When cooperating with DRV Slim with a built-in motion sensor, the AS
curtain version should be used: SLIM N/W/E-100/150/200 /AS
Connection diagram is in the DRV Slim documentation.
When connecting the DRV Slim controller to the air curtain, disconnect and
isolate /the wires from air curtain connectors 1; 3; 6; 8. In this case, the built-in
switches are disconnected and not active.
Wires from connectors: D; D; should be disconnected and insulated only
when the curtain cooperates with DRV Slim with and built-in motion sensor.
In this case, the curtain works according to the logic contained in DRV Slim.
The device is equipped with two independently adjustable outlet
grilles. The angle should be set manually within +/- 5 °. The airflow
from the outlet grille should be directed as close as possible to the
plane of the door opening (taking into account the conditions
prevailing at the door opening).
ADVICE
In order to increase the effectiveness of the air barrier during
windy conditions, the curtain 's air stream should be directed
outside the door to create a more efficient air barrier to external
factors.
).
2
15