12. BUILT-IN CONTROL
The curtain has a built-in automation system enabling automatic operation according to the signal from the motion sensor. The device has a
fan step switch (1st step; OFF; 3rd step) and a ON-OFF switch for heating elements or valve opening. The switches are located on the right
side of the device and require free access.
The device starts automatically when motion is detected in the sensor area and works according to settings selected on the switches.
FACTORY SETTINGS: C: 2000 lux; B: 10 s; A: 6 m; heating switch - lower position
PIC. 12.1. FUNCTIONS OF BUTTONS/SWITCHES.
PIC. 12.2 ADJUSTMENT OF MOTION SENSOR PARAMETERS.
h=2,1 m
r1=0,5 m
h=2,8 m
r2=0,7 m
h=3,2 m
r3=0,9 m
PIC. 12.3 AREA OF MOTION SENSOR OPERATION AT VARIOUS
INSTALLATION HEIGHTS.
12
O
; Fan speed selector - mid position
I I – fan 3 step;
O – switching OFF the device, i.e. fan speed and
heating;
I – 1 fan step.
I – heating elements (SLIM E)/valve (SLIM W)
included;
O – heating elements (SLIM E)/valve (SLIM W)
switched off
ADVICE
activation of the heating signal is signaled by a red
switch backlight
C - light sensitivity; range [10 lux ... 2000 lux];
B - switch off delay; range [10 s ... 420 s];
A - sensor range adjustment; range [2-6 m].
ADVICE
If the movement detection area is too large, the actuation area
should be adjusted first (see PIC 12.3 and 12.4)
PIC. 12.4 ADJUSTMENT OF THE AREA OF MOTION SENSOR
O
.
ACTIVITY.