1.6.4 Remote Control

The product can be operated remotely in two ways.
Use of only an external switch.
With a Phoenix Multi Control anel.
For connection of the switch see Appendix A.
Observe the following when using only an external switch:
Only functions if the switch on the product is switched to the "on" position.
Not to be connected if a remote control panel is connected.
For connection of the remote control panel, see Appendix A.
Observe the following when using a remote control panel:
Only functions if the switch on the product is switched to the "on" position.
1.6.5 External Relay (Multi/ MultiPlus)
The maximum current that can be switched through from the AC input to the AC output is 16
A (optional: 30 A). At more than 16 A an external contactor is needed: please consult your
supplier.
1.6.6 Parallel Connection
The product can be connected in parallel using several identical models, see Appendix G.
The batteries must be connected in accordance with Appendix E or F. This requires
interconnecting the products with the aid of a special cable to be supplied by Victron
Energy, in conjunction with a connection diagram.
Parallel connection requires compliance with the following conditions:
No more than five units should be connected in parallel.
Only identical models should be connected in parallel (exception: for MultiPlus
functionality only the Master needs to be a MultiPlus).
Ensure sufficient battery capacity is available.
The prescribed cable cross sections (between battery and distribution point) must be
multiplied with the number of appliances to be connected in parallel.
Position the products close to each other but ensure there is adequate clearance for
ventilation, min.10 cm.
The temperature sensor, voltage sensor and remote control must be connected to the
master.
The cables for each appliance must be equal in length (AC and DC).
1.6.7 3-phase operation
The Phoenix Multi/MultiPlus can also be used in a 3-phase system, see Appendix 0. The
batteries must be connected in accordance with Appendix E or F. The following conditions
should be complied with in the case of 3-phase operation:
Only identical models should be used.
Ensure sufficient battery capacity is available.
Position the products close to each other but ensure there is adequate clearance for
ventilation (min. 10 cm)
The temperature sensor and voltage sensor should preferably be connected to all
three products.
Only a single remote control can be connected, using splitters.