Download Inhoudsopgave Inhoud Print deze pagina

Absorption Time/ Maximum Absorption Time (Default: 4 Hours) - Victron energy Phoenix Multi 12/2000/100 Installatiehandleiding

Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

2.3.6.5 Absorption Voltage
The absorption voltage can be set at 12-16/ 24-32/ 48-64V. The battery, the T-sense and V-
sense must be disconnected during setting.
Set the DS 3-7
Set the absorption voltage
Determine the required absorption
DS-8
voltage Vq.
DS-7
off
Determine the setting number.
DS-6
off
DS-5
off
DS-4
off
DS-3
off
24)/0,1
DS-2
Determine the LED indication.
DS-1
Press the pushbuttons until the
required LED indication is
displayed.
Increment size is 0.05 V.

2.3.6.6 Absorption Time/ Maximum Absorption Time (default: 4 hours)

This setting defines the absorption period in the case of the fixed charging characteristic
and the maximum absorption time in the case of the adaptive charging characteristic.
The (maximum) absorption time can be set from 1 to 8 hours.
Set the DS 3-7
Set the (maximum) absorption time
Determine the required (maximum)
DS-8
absorption time Tq.
DS-7 on
Determine the setting number.
DS-6
off
DS-5 on
DS-4 on
DS-3
off
Determine the LED indication.
DS-2
Press the pushbuttons until the
DS-1
required LED indication is
displayed.
Increments are 1 hour.
14
Scale = 0.1V
Offset = 12/24V
Setting number = (Vq-
Scale = 1 hour
Offset = 0
Setting number = Tq
Example
Required: absorption voltage is
28.5V.
Setting number= (28.5-24)/0.1 =
45.
LED indication =
0
0
0
1
2
2
2
2
4
5
Example
Required: (maximum) absorption
time is 4 hours.
Setting number = 4.
LED indication =
0
0
0
0
0
2
0
2
0
4

Advertenties