2.3.3 Reading LEDs – on-off (Multi/ MultiPlus)
In addition to the facility of setting a value, there is an on- off facility. This allows for
switching on/ off a particular setting, or for activating/ deactivating it. The left-hand column
offers possibility A and the right-hand column offers possibility B in the case of a dual choice
setting.
A
B
A
=A
The default setting is always A.
The definitions for A and B are shown with the value to be set.
2.3.4 System Frequency (default: 50 Hz, with 45 – 65 Hz tracking range of AC input
(Multi/MultiPlus only, see note below))
The product can operate at 50Hz as well as at 60Hz.
Set the DS 3-7
Specify the frequency
Specify the required frequency.
DS-8
The default setting is 50Hz.
DS-7
off
The left row of LEDs is for 50Hz.
DS-6
off
The right row of LEDs is for 60Hz.
DS-5 on
Press the buttons until the required
DS-4
off
LED indication appears.
DS-3
off
DS-2
DS-1
Note:
The Phoenix inverter will operate at a fixed frequency of 50Hz or 60Hz.
The Phoenix Multi/MultiPlus will, when no AC input present, likewise operate at a fixed
frequency of 50Hz or 60Hz.
When AC input is present, it will track the input frequency from 45 to 65 Hz. This to be able
to connect to both 50Hz and 60Hz supply.
The tracking range can be reduced to 45 – 55 Hz or 55 – 65 Hz with VEConfigure.
B
=B
Example
Required: frequency is 60Hz.
LED indication =
50Hz
60Hz
9