Adjustment Logic; Cooling/Heating Switching; Ventilation - Galletti EVO Handleiding Voor Installatie En Gebruik

Voor hydronische terminals
Inhoudsopgave

Advertenties

EVO

ADJUSTMENT LOGIC

COOLING/HEATING SWITCHING

FAN SPEED
WINTER
SUMMER
AIR TEMPERATURE
WATER TEMPERATURE
OPENING VALVE
YES
NO
There are 4 different and alternative logics to select the
thermostat operating modes, according to the controller
configuration setting:
Local: chosen by the user pressing the MODE key
Distance: based on the status of digital input DI1
depending on the water temperature
In case of a water probe alarm, the mode
control returns temporarily to Local mode.
depending on the air temperature
Where:
Set is the temperature set with the arrows
NZ is the neutral zone
The operating mode of the thermostat is indicated on the
display by the symbols COOLING and HEATING.
FC66003554
Rev 01
Controller for units
USER MANUAL
IT IS strictly forbidden to reproduce this manual, even partially

VENTILATION

GENERAL ASPECTS
The control can manage two types of ventilation:
step ventilation with a set number of selectable speeds
(3 or 4);
modulating ventilation with variable speed between 0%
and 100%
The use of one or the other type of control depends on the
type of ventilator (step or modulating) installed on-board
the machine. Step adjustment itself can follow two different
logics based on the type of valve/s (ON/OFF or modulating).
In brief, the automatic adjustment logics managed by the
controller (and described in detail here below) are as follows:
step ventilation with 0N/OFF valve (or not installed) and 3
speeds, in cooling and heating mode;
step ventilation with 0N/OFF valve (or not installed) and 4
speeds, in summer and winter mode;
step ventilation with modulating valve and 3 speeds, in
summer and winter mode;
step ventilation with modulating valve and 4 speeds, in
summer and winter mode;
modulating ventilation adjustment with ON/OFF valve, in
summer and winter mode;
modulating ventilation adjustment with modulating valve.
NATURAL CONVECTION
For units with valve, by enabling the parameter from the
configuration menu, ventilation for heating is delayed by
0.5°C to allow for an initial natural convection phase.
STEP VENTILATION
Use the UP/DOWN keys to choose from the following
speeds:
Automatic SPD.:depending on set temperature and
room air temperature;
Extra-low spd: can only be selected if the unit is 2X1
(4 speeds)
Low SPEED
Medium SPD.
High SPD.