6.3 Other commands
D) Installation STATUS
"INFO": It is send a SMS informing about the Installation Status.
If no alarm exist, it is answer from Modem:
If an alarm exist, last SMS alarm is re-send.
PACKAGED type
HITACHI: AAAAAAAA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
E) Cancellation of SMS alarm
"CANCEL": This function disabled more SMS alarm repetition. If new alarms are detected, new SMS alarms are send.
It is displayed in 7 segments:
6.4 Configuration starting
6.4.1
MASTER/ SLAVE
$
Attention:
GSM services must be contracted with a field supplied SIM card .SIM card must be configured without a Pin number by using
an external mobile phone.
S et SW7-1 to ON in only one HARC-SMS and it is configured as Master.
?
Notes:
1 If any other HARCS are connected to the same HLINK systems, set them as SLAVE by setting SW7-1 in OFF.
2 If any CSNET WEB is connected to the same H-LINK system, then set HARC-SMS as Slave
6.4.2
PACKAGED/CHILLER
S et SW8-1 to OFF for Packaged application. For Chiller application set it ON
6.4.3
Frequency and duration period for alarm advising
S et SW8-3 & 4 to the desired frequency.
Example: It is desired a SMS sending frequency of 30 min.
Set SW8- & 4 in ON & ON position. In case of alarm, the corresponding SMS is send every 0 min
Available frequencies:
PMML0162A-rev.0 - 6/2008
HITACHI: AAAAAAAA: NO ALARM
CL
HARC-SMS - Installation Manual
HARC-SMS - xxxxxxxxxxxxxxxx
CHILLER type
HITACHI: AAAAAAAA
(CH): AL AA, CC...
(CH): AL AA, CC...
(CH): AL AA, CC...
(CH): AL AA, CC...
(CH): AL AA, CC...
1
1
1