SW7 – FUNCTIONS SETTING 1
SW7
Description
Configuration as MASTER HARC-SMS: SW7-1: ON
Only one HARC-SMS must be set as Master HARC-SMS.
Note: If there is any Central control like CSNET WEB, then all HARC-SMS must be set as SLAVE.
Configuration as SLAVE HARC-SMS: SW7-1: OFF
It must be one HARC-SMS configured as MASTER, all the rest of HARC-SMS must be configured as
SLAVE.
HARC-SMS feedback signal
Feedback signal disabled
Feedback signal enable with a frequency of 1 month
Feedback signal enable with a frequency of 1 week
Feedback signal enable with a frequency of 1 day
n
SW8 – FUNCTIONS SETTING 2
SW8
Description
SW8-1: Packaged and Chiller setting
SW8-1 – It is set in ON position when monitored units are Chiller type
SW8-1 – It is set in OFF position when monitored units are Packaged type
SW8-2 – Enable / Disable communications
SW8-2 – It is set in ON to allows the disconnection of SMS Alarm sending. It is useful during
maintenance works, commissioning, ..., when technicians are assisting the installation and no SMS are
required. Disconnection is done in ON position.
SW8-2 – Factory setting in OFF. SMS alarm is enabled
SW8-3 & 4 – SMS Sending frequency
SW8-3 & 4 – OFF & OFF
- 1 SMS sent every 12 h
SW8-3 & 4 – ON & OFF
- 1 SMS sent every 1h
SW8-3 & 4 – OFF & ON (Special frequency)
- 1 SMS sent every 15min (during first h)
- 1 SMS sent every 1h (rest of the 1st day)
- 1 SMS sent per day (from 2nd day)
SW8-3 & 4 – ON & ON
- 1 SMS send every 0 min
Note: These frequencies must be set accordingly to advising period (SW8-5&6)