HARC-SMS - Installation Manual
HARC-SMS - xxxxxxxxxxxxxxxxxx
12
12
6.1 SMS Alarm contents
In case of any alarm appear in a Hitachi installation, SMS are sent to any Mobile number registered.
PACKAGED type
HITACHI: AAAAAAAA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
Where:
"AAAAAAAA": Installation name; Maximum length of 16 characters
In case of Packaged:
"(OU,IU): AL AA": "OU" corresponds to OU address, "IU" corresponds to IU address, "AL" means alarms and "AA" is detected
Alarm code.
In case of Chiller:
"(CH): AL": "CH" corresponds to Chiller Address, "AL" means alarms
"AA": means general Chiller alarm
"CC": means first detected cycle alarm ; if more cycle alarms are detected, it is shown "..."
If more than 5 alarms are detected, then SMS is send as follows:
PACKAGED type
HITACHI: AAAAAAAA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
(OU, IU): AL AA
Multiple alarms
?
Note:
HARC-SMS never detects any alarm caused by the disconnection, communication failure or similar of a IU. Communication
alarm is only found if a existing IU is sending communication alarm (alarm codes: 03 or 32)
6.2 Mobile number configuration
Mobile numbers are registered as follows:
Configuration is done by using any mobile phone and sending a specific SMS message to the HARC-SMS as follows:
A) Mobile number registering:
First of all is required to set SW8-7 in ON position
Take any Mobile and create and sent a SMS as follows
"SET XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX"
Where X = Mobile phone numbers. Maximum length is 16 numbers.
Each mobile phone number must be separated by one blank space
Other functions related are:
B) Mobile phone number delete:
"DEL" : From any Mobile it is sent to HARC-SMS and all Mobile numbers in the list are deleted
C) Mobile phone numbers list reminder:
"LIST"; From any Mobile it is sent to HARC-SMS and it is answered Mobile number list inside HARC-SMS
CHILLER type
HITACHI: AAAAAAAA
(CH): AL AA. CC
(CH): AL AA. CC
(CH): AL AA. CC
(CH): AL AA. CC
(CH): AL AA. CC
CHILLER type
HITACHI: AAAAAAAA
(CH): AL AA. CC...
(CH): AL AA. CC...
(CH): AL AA. CC...
(CH): AL AA. CC...
(CH): AL AA. CC...
Multiple alarms
HITACHI: AAAAAAAA
1: XXXXXXXXXXXXXXXX
2: XXXXXXXXXXXXXXXX
3: XXXXXXXXXXXXXXXX
4: XXXXXXXXXXXXXXXX
5: XXXXXXXXXXXXXXXX
PMML0162A-rev.0 - 6/2008