√ All work described below is in compliance with NEN 3140.
√ Check whether the proper order has been maintained for the connecting
terminals.
√ Check whether the cores have been properly tightened, 3.5 to 5 Nm.
√ Check whether the ground connection has been made with the supplied
grounding.
√ Check whether the cable thickness of the power cable matches the fused
current rating.
√ Check whether the charging station is tightly and properly secured.
√ Check whether the station is sufficiently waterproof.
√ Keep the immediate environment of the work area free from obstacles.
18. USER / INSTALLATION MANUAL
18.1 Required power cable
The power cable has to be connected to a separate power group.
When using a machine this should be C characteristic or equal, the height of
the current rating depends on the length and the available power on site.
PLEASE NOTE: the charging station requires only 1 power
cable. Please take into account the cables and groups will be
under full load for several hours.
Cabling will have to be implemented in accordance with current standards,
such as NEN1010.
Exceptions to the NEN1010 standard are:
• Cable thickness deviates
• Grounding spread resistor < 30 Ohm.
• Installation resistor < 1 Ohm.
• Voltage drop max. 2%.
19. WALL INSTALLATION
We recommend mounting the charging station to the wall at a height of +/-
85 centimetres, measured from the bottom of the charging station.
When mounting the charging station, you should take into account the
strength of the wall. The wall should be completely closed, without any holes
or openings. If these are present, they must first be filled.
Use the right fastening screws to firmly secure the charging station to the
wall and use all four fastening holes. Mounting material is included.
First, remove the cover with a torx screw at the bottom. The charging station
can now be mounted to the wall.
Insert the cable into the charging station and fasten it with a cable gland.
17