6.2

Meaning of the different parameters

(Text in bold = default values)
P0
Operating mode
Values
1: sequential
2: sequential + short closure time-delay (60 s)
3: sequential + long closure time-delay (120 s) + blockage of cells (2 s)
Comments
1: Each press on the remote control causes the motor to move (initial position: door
closed) as per the following cycle: open, stop, close, stop, open, etc.
2: This operating mode is only authorised if photoelectric cells are installed and P3 = 2.
In sequential mode with short closure time-delay:
3: This operating mode is only authorised if photoelectric cells are installed and P3 = 2 .
In sequential mode with long closure time-delay + blockage of the cells:
P1
203 V auxiliary output
Values
1: orange light
2: area lighting
Comments
1: Fixed advance warning of 2 s.
2: The lighting comes on as soon as the motor starts and goes off 60 seconds after the
motor has come to a complete stop.
P2
Hard-wired safety edge safety input
Values
1: optical
2: resistive 1.2 kΩ
3: resistive 8.2 kΩ
4: inactive
Comments
DANGER! If P2 = 4, the safety is inactive. Parameter setting reserved
exclusively for a diagnostic.
P3
Photoelectric cell safety input
Values
1: active
2: active with auto-test by means of switching
3: active with autotest via test output
4: inactive
• the door will close automatically after a time-delay of 60 s,
• pressing a button on the remote control interrupts the movement taking place
and the closure time delay (the door remains open).
• the door will close automatically after a time-delay of 120 s.
• pressing a button on the remote control interrupts the movement taking place
and the closure time delay (the door remains open).
• after the door is opened, movement in front of the cells (safe closure) will close
the door after a short timed delay (fixed at 2 s). If no movement occurs in front of
the cells, the door will close automatically after a time-delay of 120 s. If there is
an obstacle in the cells' detection zone, the door will not close. It will close once
the obstacle is removed.