Risk zones: what elimination measures can be taken?
RISKS
ZONE 1
Risk of crushing between the ground and
the lower edge of the door during closing
ZONE 2
Risk of crushing between the casing and
door
ZONE 3
Risk of cutting or trapping between the
door slats in gaps of between 8 mm and
25 mm
ZONE 4
Risk of crushing between the runners
and door
1.5
Electrical installation
DANGER
The installation of the power supply must comply with the standards in
force in the country in which the motorisation is installed, and must be car-
ried out by qualified personnel.
The electric line must be exclusively reserved for the motorisation and
equipped with protection, comprising:
a 10 A fuse or breaker,
a differential type device (30 mA).
An all-pole power supply cut-off device must be provided. The switches
provided to ensure a cut-out of all poles on fixed appliances must be con-
nected to the power supply terminals and there must be a separation
between the contacts on all poles to ensure complete disconnection in
conditions where category III high impulse voltage is present.
Low-voltage cables subject to inclement weather must be at least of type
H07RN-F.
It is recommended that you fit a lightning conductor (mandatory maximum
residual voltage 2 kV).
Cable run
Underground cables must be equipped with a protective sheath with a sufficient dia-
meter to contain the motor cable and the accessories cables.
For overground cables, use a cable grommet that will withstand the weight of
vehicles.
26
SOLUTION
Obstacle detection by the safety edge
solution.
Obstacle detection must be confirmed as
compliant with Appendix A of standard
EN 12 453
For operation with automatic closing, in-
stall photoelectric cells.
Eliminate any gap ≥ 8 mm or ≤ 25 mm
between the casing and door.
Eliminate all sticking points and all sharp
edges from the surface of the door
Eliminate any gap ≥ 8 mm or ≤ 25 mm
Eliminate any sharp edges from the run-
ners
Eliminate any gap ≥ 8 mm between the
runners and the door
SIMUDRIVE SD100Hz