Specificaties
380-480 V
Behuizing
Vermogen [kW]
A2
A3
A4
A5
B1
B2
B3
B4
C1
8
8
C2
C3
C4
Tabel 8.14 380-480 V, behuizingstype A, B en C
62
Bedieningshandleiding VLT
Aanbevolen
zekeringgrootte
1.1-4.0
gG-10 (0,37-3)
gG-16 (4)
5.5-7.5
gG-16
1.1-4.0
gG-10 (0,37-3)
gG-16 (4)
1.1-7.5
gG-10 (0,37-3)
gG-16 (4-7,5)
11-18,5
gG-40
22-30
gG-50 (18,5)
gG-63 (22)
11-18
gG-40
22-37
gG-50 (18,5)
gG-63 (22)
gG-80 (30)
37-55
gG-80 (30)
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
45-55
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
®
AQUA Drive FC 202
Aanbevolen
max. zekering
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160
aR-250
gG-150 (37)
gG-160 (45)
aR-250
MG20MA10 - Rev. 2014-01-15
Aanbevolen circuit-
Max. uitschakelniveau
breaker
Moeller
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
[A]
25
25
25
25
63
100
50
100
160
250
150
250