Download Inhoudsopgave Inhoud Print deze pagina

Acquisitions Retrieved Cyclically - Oldham MX43 Gebruikershandboek

Digitale en analoge meetcentrale
Verberg thumbnails Zie ook voor MX43:
Inhoudsopgave

Advertenties

Acquisitions retrieved cyclically

Real address
SENSOR
MEASUREMENTS
[256 + 8]
Start: 2001
Sensor measurement
end : 2264
Real address
ALARMS [256 + 8]
Start: 2301
Table of activated
end : 2564
alarms
Real address
INFO
2600
CRC32 of the general
configuration
2601
2602
Second counter
2603
Nb
Data type
bytes
2
Table with 264 total 16 bit symbols
where the measurements are listed
at their address. The measurement
being whole, the automatic system
uses the Display format field to
determine where to position the
comma.
Nb
Data type
bytes
Table with 264 total 16 bit non
2
symbols where the alarms bits are
listed at their address.
ALARM_1
ALARM_2
ALARM_3
UNDERSCALE
OVERSCALE
AL_DEFAULT
AL_OUT_OF_RANGE
L_VERIFICATION
Bits 8 to 16 not in use
Nb
Data type
bytes
2
32 most significant bits option.
Note: CRC32 of the entire
configuration except the relays
(from 0x78000 to 0x7AFFC). If
different, re-upload the
configuration.
2
32 least significant bits option.
32 most significant bits option;
Note: this counter increases every
2
second and verifies that the unit is
active.
2
32 least significant bits option.
11- RS485 digital output
(bit 0)
(bit 1)
(bit 2)
(bit 3)
(bit 4)
(bit 5)
(bit 6)
(bit 7)
77