SMOKE OUTLET
The insert must have its own smoke outlet (the smoke can-
not be discharged into a smoke flue used by other devices).
Smoke discharge takes place from the mouth on the cover,
measuring 8 cm in diameter.
The smoke outlet must be connected to outside by means of
suitable steel pipes EN 1856 certified.
The pipe must be hermetically sealed.
The material used to seal and if necessary insulate the pipes,
must be resistant to high temperatures (high temperature silico-
ne or mastic).
The only horizontal section allowed may be up to 2 m long up
to three 90° bends (in relation to the vertical).
A vertical section of at least 1.5 m and an anti-wind terminal
is necessary (if the discharge outlet is not in a chimney flue -
reference UNI 10683).
The vertical duct can be internal or external.
If the smoke channel is outside, it must be appropriately insu-
lated.
If the smoke channel is fitted inside a chimney flue, the latter
must be suitable for solid fuel.
If it is wider than 150 mm in diameter it must be improved by
entering a pipe that has a suitable cross-section and is made of
suitable material (e.g. 80 mm diameter steel).
All sections of the smoke duct must be accessible for inspec-
tion.
The chimney pots and smoke ducts connected to the solid fuel
appliances must be cleaned once a year (verify whether a speci-
fic legislation exists in your country).
Failure to regularly inspect and clean the insert increases the
probability of a fire occurring in the chimney pot. In that case,
proceed as follows:
Do not use water to extinguish the fire; Empty the pellet hop-
per; Contact specialist personnel before reigniting the stove.
The insert is designed to work under any weather conditions.
In case of particular conditions, such as strong wind, the safety
system may be activated, which results in the insert being
extinguished.
If this happens, do not operate the insert with the safety devices
disabled.
If the problem persists, contact our Technical Service De-
partment.
INSTALLATION
A: internal chimney flue up to the roof
B: external brick-built chimney flue
C: internal brick-built chimney flue
D: double-wall external steel chimney
flue (for the following installation, the chimney flue must be
double-walled and well-insulated for the entire length)
CHIMNEY POT
The main characteristics are:
- an internal cross-section at the base, which is the same as that
of the chimney flue
- an outlet cross-section which is no smaller than twice that of
the chimney flue
- its position must be high enough to catch the wind and avoid
downdraft areas in turbulent wind, it must be high enough to
catch the wind and avoid downdraft areas in turbulent wind.