Installation
6
Installation
The cooling device is designed for free-standing installation, but can be built-
in if the following conditions are complied with to ensure satisfactory opera-
tion and maximum cooling efficiency.
The cooling device must be levelled carefully to ensure proper function.
The clearance between the cooling device's back and the wall should be
20 mm or more.
Ventilation must be provided as shown in alternatives A, B, C or D (fig. 2,
page 3).
The ventilation duct must at least measure 105 mm* x the width of the
cooling device.
Only the entire cooling unit must project into the ventilation duct as shown
(fig. 2, page 3).
Air passing through the ventilation duct must not be preheated by any
source of heat.
Ventilation grills, if used, must have openings of at least 200 cm² each.
For glass door version, when ambient humidity is above 65 % in 25 °C
ambient temperature, moisture will condense on the door.
The cooling device can be fixed to the bottom of the furniture through its
fixing feets using screws of an appropiate length (fig. 3, page 3).
The socket outlet for the mains connection must be freely accessible.
8
RH430, RH440
EN