Download Inhoudsopgave Inhoud Print deze pagina

Technical Data; Fault Finding Chart - Grundfos MAGNA 2000 Series Montage-Instructies

Lon
Inhoudsopgave

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 28
4. Indicator light
The LON module incorporates a yellow indicator light which is a service LED
indicating various conditions of the LON network.
For further information, see the documentation files on the floppy disk sup-
plied with the LON module.

5. Technical data

Transceiver type
Recommended cable
Transmission speed
Protocol
Current consumption

6. Fault finding chart

Fault
Cause
The pump does not
The wires are not con-
react to the LON
nected correctly to the
signal.
terminal block.
The plug connection be-
tween the terminal box
and the module is faulty.
The terminal box or the
module is defective.
The yellow indica-
The LonWorks network or
tor light on the
the module is defective.
module is not off
(flashing or perma-
nently on).
FTT - 10
Twisted-pair cable
78 kBits/s
®
LonTalk
Maximum 200 mA
Remedy
Connect the wires cor-
rectly.
Correct the fault.
Replace the module.
Replace the terminal box.
Contact Grundfos.
Contact the system ad-
ministrator for further de-
tails and fault finding.
Subject to alterations.