Maintenance
Internal unit error list
ERROR
DESCRIPTION
1
14
Outdoor Sensor Damaged
4
20*
Bus supply overload
7
01
Zone1 Send Probe Damaged
7
02
Zone2 Send Probe Damaged
7
03
Zone3 Send Probe Damaged (N/A)
7
11
Zone1 Return Probe Damaged
7
12
Zone2 Return Probe Damaged
7
13
Zone3 Return Probe Damaged (N/A)
7
22
Zone2 Overheat
7
23
Zone3 Overheat
9
02
System fl ow sensor damaged
9
10
HP communication error
9
23
Low pressure error
Ebus Communication error between EM and
9
24
TDM
9
33
Overheat
9
34
DHW Tank sensor damaged
9
35
Tank overtemperature
9
36
Floor Thermostat 1 error
9
37
No circulation error
9
38
Anode Fault
9
40
Hydraulic scheme not defi ned
9
41
HIV IN1 not defi ned
9
42
HIV IN2 not defi ned
9
44
Cooling overtemperature
9
45
Flow switch stuck
9
46
HP compressor error
9
55
Water fl ow switch
9
58
Buff er temperature sensor
9
59
Buff er over-temperature
P2 circulator confi guration not aligned with hy-
9
70
draulics. Check for auxiliary pump confi guration
9
71
External unit Version undefi ned
2
P2
Antilegionella not completed
32 / GB
TROUBLESHOOTING
Activation of thermoregulation based on outdoor sensor and outdoor
sensor not connected or damaged
Flow sensor not connected or damaged
- Check the wiring connection of the modbus cable.
- Red led on TDM not blinking-> change TDM control board
Check water leakage of the hydraulic circuit
- Water pressure switch damaged
- Wiring of water pressure switch damaged
- Check wiring connection between TDM end Energy Manager
- Check water fl ow of the heating circuit
- DHW tank sensor not connected or damaged
- Check 3-way valve (DIV1) blocked in DHW position
- Check water circulation of the underfl oor zone
- Check main circulation activation
- Check water fl ow sensor detection by par. 17.11.3
Check anode connection
- Check water presence in the tank
- Check anode status
- Hydraulic scheme not selected by parameter 17.2.0
Function not selected by parameter 17.1.0
Function not selected by parameter 17.1.1
- Check water fl ow of the cooling circuit
Check if main circulation is active before the heat request
- Check the water fl ow detection by water fl ow sensor (see par. 17.11.3)
before the heat request
Check the compressor's frequency after the end of the heating demand via
parameter 17.12.1
Check the fl ow temperature sensor and return temperature sensor place-
ment.
Buff er charge inhibited
Buff er charge inhibited
Warning displayed for 30 seconds and stored in the historical
Warning displayed for 30 seconds and stored in the historical
Antilegionella setpoint temperature not reached in 6 hours
- Check DHW tapping during antilegionella cycle
- Check fl ow temperature during antilegionella cycle
- Check heating resistors activation