BFT GIOTTO 30 S BT Gebruikers- En Installatiehandleiding pagina 26

Inhoudsopgave

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 47
1-2
Control for cooling fan 230V~ ±10% (1=L) (2=N)
3-4
Not used
6-7
Motor connections
15-5
Motor connections, closing reference
15-8
Motor connections, opening reference
9-10
Flashing light (24 V~, 25W)
Accessories power supply:
24 V operation with mains power on.
11-12
24 V (11+,12-) operation with no mains power and optional
buffer battery kit.
Safety device power supply output (photocell transmitter).
N.B.: output active only during operating cycle.
13-14
24 V Vsafe operation with mains power on.
24 V (13+,14-) Vsafe operation with no mains power and
optional buffer battery kit.
START button (N.O.)
15-16
This option can be set via the "logic menu".
Start - operation according to 2-3-4 step logic.
STOP input (N.C.)
15-17
The command stops movement.
If not used, leave jumper inserted.
PHOTOCELL input (N.C.).
15-18
Operation according to photocell during opening logic.
If not used, leave jumper inserted.
19
Safety device test input FAULT - PHOT (N.O.).
SAFETY EDGE input BAR (N.C.).
The command reverses movement during closing and stops
15-20
movement during opening.
If not used, leave jumper inserted.
Barrier-open warning light output (N.O. contact, 24V~/ 3W max)
21-22
or, in alternative, alarm output (see Table "B", Alarm SCA) and
Connection To Parky Car-Park Management System
23-24-
Encoder inputs
25-26
OPEN/ TIMER control button (N.O.)
Open - Gate opened with this command.
15-27
Timer - If the contact is closed, the leaves open and stay open
until the contact is opened. If the contact connected is open,
the leaves close and are ready for normal operation.
Close button CLOSE (N.O.)
15-28
The command causes the leaf to close.
14) SAFETY DEVICES FIG. H
Note: only use receiving safety devices with free changeover
contact.
14.1) NON-TESTED DEVICES FIG. H1
14.2) TESTED DEVICES FIG. H2, H3
15) ADJUSTMENTS
RECOMMENDED ADJUSTMENT SEQUENCE:
Adjusting the limit switches Fig.I (
Programming remote controls
Setting of parameters/logic, where necessary
16) PARAMETERS MENU (para )
(TABLE "A" PARAMETERS)
17) LOGIC MENU (logic)
(TABLE "B" LOGIC)
18) RADIO MENU (RADIO)
Logic
Description
Add Start Key
add start
associates the desired key with the Start command
Erase List
WARNING! Erases all memorized remote controls
erase 64
from the receiver's memory.
Read receiver code
cod RX
Displays receiver code required for cloning remote controls.
ON = Enables remote programming of cards via a previously me-
morized W LINK transmitter. It remains enabled for 3 minutes
v
from the time the W LINK remote control is last pressed.
OFF=W LINK programming disabled.
26
- GIOTTO 30-60 S BT / GIOTTO 30-60 BT
INSTALLATION MANUAL
)
See reference section
- IMPORTANT NOTE: THE FIRST TRANSMITTER MEMORIZED MUST
BE IDENTIFIED BY ATTACHING THE KEY LABEL (MASTER).
In the event of manual programming, the first transmitter assigns the
RECEIVER'S KEY CODE: this code is required to subsequently clone the
radio transmitters.
The Clonix built-in on-board receiver also has a number of important
advanced features:
• Cloning of master transmitter (rolling code or fixed code)
• Cloning to replace transmitters already entered in receiver
• Transmitter database management
• Receiver community management
To use these advanced features, refer to the universal handheld pro-
grammer's instructions and to the CLONIX Programming Guide, which
come with the universal handheld programmer device.
19) DEFAULT MENU (default)
Restores the controller's default factory settings.
20) LANGUAGE MENU (language)
Used to set the programmer's language on the display.
21) STATISTICS MENU
Shows:
- board version
- number of total manoeuvres made by the automation
- number of remote controls saved to the built-in receiver
22) CONNECTION TO PARKY CAR-PARK MANAGEMENT SYSTEM
The board can be configured in order to make an output available for
controlling the barrier status. When the SCA Alarm logic is disabled (OFF)
and the Alarm Time parameter is set to 0 s, the SCA contact (21-22) is
configured as follows (Fig. G):
- contact closed between terminals 21-22 with the barrier lowered
- contact open between terminals 21-22 with the barrier lifted
22.1) SERIAL CONNECTION USING SCS1 BOARD (Fig. AE)
The LIBRA-C-G/LIBRA-C-GS control panel allows several automation
units (SCS1) to be connected in a centralised way by means of appropri-
ate serial inputs and outputs. This makes it possible to use one single
command to open and close all the automation units connected.
Following the diagram in Fig. AE, proceed to connecting all the LIBRA-
C-G/LIBRA-C-GS control panels, exclusively using a telephone-type line.
Should a telephone cable with more than one pair be needed, it is
indispensable to use wires from the same pair.
The length of the telephone cable between one appliance and the
next must not exceed 250 m.
At this point, each of the LIBRA-C-G/LIBRA-C-GS control panels must
be appropriately configured, by setting a MASTER unit first of all, which
will have control over all the others, to be necessarily set as SLAVE (see
logic menu).
Also set the Zone number (see parameter menu) between 0 and 127.
The zone number allows you to create groups of automation units, each
one answering to the Zone Master unit. Each zone can only be assigned
one Master unit, the Master unit in zone 0 also controls the Slave
units in the other zones. WARNING: the control panel set as the master
must be the first in the series.
22.2) Opposite Barriers (Fig. AF)
By means of a serial connection, it is also possible to obtain centralised
control of two opposite barriers/gates.
In this case, the Master M1 control panel will simultaneously manage
closing and opening for the Slave M2 control panel.
SETTING REQUIRED FOR OPERATION:
- MASTER board: zone=128, aster=ON
- SLAVE board: zone=128, aster=OFF
WIRING REQUIRED FOR OPERATION:
- The MASTER and SLAVE control units are interconnected through the
4 wires (RX/TX) for the SCS1 interface boards;
- All the activation controls, as well as the remote controls must refer to
the MASTER board;
- All the photocells must be connected to the MASTER control panel;
- The safety edges of the MASTER leaf must be connected to the MASTER
control unit;
- The safety edges of the SLAVE leaf must be connected to the SLAVE
control unit.
23) LIMIT SWITCH SETTING
WARNING: before opening the door, the spring must be unloaded
(vertical boom). The barrier is provided with programmable electronic limit
switches and mechanical stop devices. There must be a rotation margin
(about 1°) on closing and opening between the electrical limit switches
and mechanical stop devices (Fig. J). To evaluate correctly the values set,
you are advised to carry out a few complete consecutive manoeuvres.
24) EMERGENCY RELEASE (Fig. Y)
WARNING! When an actuator without bar needs to be released, ensure
that the balancing spring is not compressed (bar in the opening position).