10 Technical data
Supply voltage
Motor protection
Type of protection
Winding category
Temperature category
Media temperature
Ambient temperature
Operating pressure
Inflow pressure
Noise
Electromagnetic
compatibility
EEI-values
1×230 V ±10%, 50/60 Hz, PE
External motor protection is not required
IP 44 (EN 60529)
Insulation category F
TF 110 (EN 60335-2-51)
+2°C to +110°C
The temperature of the medium must be higher than the am-
bient temperature to prevent condensation water from forming
in the terminal box and the stator.
Ambient temperature
°C
0
15
30
35
40
If the medium temperature is below the ambient
temperature, the pump head and connector must
be set in the 6 o'clock position.
0°C to +40°C
Max. 10 bar, 102 m, 1 MPa
Minimunm inflow pressure
Media
temperature
[bar]
≤ +75 °C
0.05
+90 °C
0.28
+110 °C
1.08
Sound pressure level under 43 dB(A)
EMV guidelines (2004/108/EC)
Standards: EN55014-1:2006, EN55014-2:1997
PrimAX xx-3 = EEI ≤ 0.15
PrimAX xx-4 = EEI ≤ 0.16
PrimAX xx-6 = EEI ≤ 0.17
PrimAX xx-8 = EEI ≤ 0.18
Media temperature
Min. °C
2
15
30
35
40
[m]
0.5
2.8
10.8
english
97
|
Max. °C
110
110
110
90
70
[MPa]
0.005
0.028
0.108