Waardebereiken en fabrieksinstellingen
6.3.7 WB 5000A-11/6000A-11
Naam
AID-Esk-Alpha*
Operating Mode
Control
DGS-HystVolNom*
DGS-PWMVolNom*
E_Total
Fac-delta--*
Fac-delta+*
Fac-delta+Fast*
Fac-delta-Fast*
Fac-Limit delta
Fac-Max-Fast-Tm*
Fac-Max-Tm*
Fac-Min-Fast-Tm*
Fac-Min-Tm*
Fac-Start delta
Fan-Test
FrqCtl-ReconMax*
FrqCtl.ReconMin*
GndFltRea
GriFltMonTms*
GriFltReConTms*
GriStrTms*
h_Total
Inst.-Code
KI-Wind-Reg
KP-Wind-Reg
P-GriSwOpnZerW
74
SB_SMC_WB_Par-TB-TNL113160
Waarde/bereik
0 grd/% ... 40 grd/%
Mpp-Operation
V-Const
Stop
Turbine
Auto
Bridge
0 % ... 60 %
40 % ... 100 %
0 kWh ... 200 000 kWh
0,1 Hz ... 6 Hz
0,1 Hz ... 5 Hz
0,1 Hz ... 5 Hz
0,1 Hz ... 6 Hz
0 Hz ... 5 Hz
0,04 s ... 10 s
0,04 s ... 90 s
0,04 s ... 300 s
0,04 s ... 300 s
0 Hz ... 5 Hz
0
1
50 Hz ... 65 Hz
44 Hz ... 60 Hz
GndFltWrn
GndFltDscon
0 s ... 1 600 s
0 s ... 1 600 s
0 s ... 1 600 s
0 h ... 200 000 h
0 ... 4 000 000 000
0 ... 0,25
0 ... 0,25
No
Yes
SMA Solar Technology AG
Standaardwaarde
Afhankelijk van landspecifieke norm
Turbine
(Als u onder "Memory Function" de instelling
"Default Param." kiest, moet u de parameter
"Operating Mode" vervolgens weer
handmatig op "Turbine" instellen.)
Auto
5 %
70 %
0 kWh
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
2 Hz
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
1 Hz
0
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
GndFltWrn
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
0 h
0
0,005
0,02
No
Technische beschrijving