Waardebereiken en fabrieksinstellingen
6.2 Sunny Mini Central
6.2.1 SMC 4600A/5000A/6000A
Naam
ACVtgRPro*
AID-Esk-Alpha*
AntiIsland-Ampl*
AntiIsland-Freq*
Operating Mode
Control
dFac-Max*
E_Total
Fac-delta--*
Fac-delta+*
Fac-delta+Fast*
Fac-delta-Fast*
Fac-Limit delta
Fac-Max-Fast-Tm*
Fac-Max-Tm*
Fac-Min-Fast-Tm*
Fac-Min-Tm*
Fac-Start delta
Fan-Test
GndFltRea
h_Total
LDVtgC*
P-HzStop*
P-HzStr*
P-W* (SMC 4600A)
P-W* (SMC 5000A)
40
SB_SMC_WB_Par-TB-TNL113160
Waarde/bereik
230 V ... 300 V
0 grd/% ... 40 grd/%
0 grd ... 10 grd
1 mHz ... 2 000 mHz
Mpp-Operation
V-Const
Stop
Turbine
Auto
Grid
Bridge
0,1 Hz/s ... 6,0 Hz/s
0 kWh ... 200 000 kWh
0,1 Hz ... 6 Hz
0,1 Hz ... 5 Hz
0,1 Hz ... 5 Hz
0,1 Hz ... 6 Hz
0 Hz ... 5 Hz
0,04 s ... 10 s
0,04 s ... 10 s
0,04 s ... 300 s
0,04 s ... 300 s
0 Hz ... 5 Hz
0
1
GndFltWrn
GndFltDscon
0 h ... 200 000 h
0 V ... 50 V
0 Hz ... 5 Hz
0 Hz ... 5 Hz
0 W ... 5 000 W
0 W ... 5 500 W
SMA Solar Technology AG
Standaardwaarde
253 V
Afhankelijk van landspecifieke norm
0 grd
500 mHz
Mpp-Operation
Auto
Afhankelijk van landspecifieke norm
0 kWh
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
2 Hz
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
Afhankelijk van landspecifieke norm
1 Hz
0
GndFltWrn
0 h
Afhankelijk van landspecifieke norm
0,05 Hz
0,20 Hz
5 000 W
5 500 W
Technische beschrijving

Advertenties

Inhoudsopgave
loading

Inhoudsopgave