THERMODYNAMIC PERFORMANCE OF EXTERNAL UNIT IN HEATING/COOLING MODE
MODEL
Data at Eurovent LCP /A/CHF conditions*
Nominal heating capacity
Power input
COP
Eurovent class, heating
Nominal cooling capacity
Power input
EER
Eurovent class, cooling
Data at Eurovent LCP /A/AC conditions**
Nominal heating capacity
Power input
COP
Eurovent class, heating
Nominal cooling capacity
Power input
EER
ESEER part-load performance
Eurovent class, cooling
Nominal heating capacity, radiator applications***
Power input
COP
Net water volume
Maximum water-side operating pressure
Water pressure drop, X version (CHF)
Water connections, inlet/outlet (MPT gas)
Netto watervolume
Maximum waterzijdige bedrijfsdruk
Drukverlies water, X versie (CHF)
Wateraansluitingen, ingang/uitgang (MPT gas)
Ventilators Propellerventilators
Aantal/diameter
Aantal schroeven
The water heat exchanger fouling factor is 0 (m
*
Standard Eurovent LCP/A/CHF conditions in heating mode: water heat exchanger entering/leaving water temperature 30 °C/35 °C, outside air temperature 7 °C db/6 °C wb.
Standard Eurovent LCP/A/CHF conditions in cooling mode: water heat exchanger entering/leaving water temperature 23 °C/18 °C, outside air temperature 35 °C.
**
Standard Eurovent LCP/A/AC conditions in heating mode: water heat exchanger entering/leaving water temperature 40 °C/45 °C, outside air temperature 7 °C db/6 °C wb.
Standard Eurovent LCP/A/AC conditions in cooling mode: water heat exchanger entering/leaving water temperature 12 °C/7 °C, outside air temperature 35 °C.
*** Conditions in heating mode: entering/leaving water temperature 55 °C/a, outside air temperature 7 °C db/6 °C wb. Performances are in accordance with EN 14511.
**** Based on the following conditions: entering/leaving water temperature 35 °C/30 °C, outside air temperature 7 °C.
† Based on the following conditions: entering/leaving water temperature 12 °C/7 °C, outside air temperature 35 °C.
Note: The sound pressure level is measured in a hemisperic fi eld at 4 m distance from the unit.
12 kW
kW
11,9
kW
3,01
kW/kW
3,95
B
kW
10.24
kW
1.17
kW/kW
2.96
B
kW
12,9
kW
4,26
kW/kW
3,03
A
B
kW
10,2
kW
3,46
kW/kW
2,96
kW/kW
4,2
B
kW
10,27
kW
4,60
kW/kW
2,79
l
0.8
kPa
300
kPa
26
in
1
mm
2/495
3
2
K)/W for all conditions.
15 kW
12 T kW
14,5
12
3,54
2,79
4,09
4,30
A
A
13.04
10.20
1.90
1.96
2.95
3
B
B
14
11,2
4,32
3,34
3,23
3,35
A
A
13
10,2
4,42
3,40
2,95
3
4,3
4,4
B
B
11,66
11,05
4,13
3,96
2,82
2,90
R-410A
DC twin-rotary
PMV
0.8
0.8
300
300
33
26
2/495
2/495
/ 45
15 T kW
15
3.57
4.20
A
13
2.91
B
14,5
4,39
3,30
A
13
4,47
2,91
4,3
B
12
4,21
2,85
0,8
300
33
2/495