dIXEL
Defrost termination temperature
Pr1
dtS
8.0
(Probe B)
Pr1
idF
6
Interval between defrosts
Pr1
MdF
30
Defrost Maximum duration
Pr1
dSd
0
Start defrost delay
Pr1
dFd
it
Display during defrost
Pr1
dAd
30
Defrost display time out
Pr1
Fdt
0
Drain down time
Pr1
dPo
n
Defrost at start-up
Defrost delay after continuous
Pr1
dAF
0.0
cycle
Fan
Pr1
FPA
P2
Fan probe A
Pr1
FPb
nP
Fan probe B
Virtual probe percentage (fan
Pr1
FPE
100
management)
Pr1
FnC
O-n
Fan operating mode
Pr1
Fnd
10
Fan delay after defrost
Temperature differential to
Pr1
FCt
10
avoid short cycles of fans
Pr1
FSt
2.0
Fan stop temperature
Pr1
FHy
1.0
Fan stop differential
Fan activation time after defrost
Pr1
Fod
0
(without compressor)
Pr1
Fon
0
Fan ON time
Pr1
FoF
0
Fan OFF time
Kind of regulation for
Pr2
trA
UAL
modulating output
Pr2
SOA
80
Fixed speed for fan
Pr2
SdP
30.0
Default Dew Point value
Differential for fan / offset for
Pr2
ASr
1.0
anti sweat heater
Proportional band for
Pr2
PbA
5.0
modulating output
Minimum output for modulating
Pr2
AMi
0
output
Maximum output for modulating
Pr2
AMA
100
output
Time with fan at maximum
Pr2
AMt
200
speed
Alarm
Pr1
rAL
P1
Probe for temperature alarm
Temperature alarm
Pr1
ALC
Ab
configuration
Pr1
ALU
10
High temperature alarm setting
Pr1
ALL
-30
Low temperature alarm setting
Differential for temperature
Pr1
AHy
1.0
alarm
Pr1
ALd
15
Temperature alarm delay
High temperature alarm setting
Pr2
dLU
150
(defrost probe)
Low temperature alarm setting
Pr2
dLL
-55
(defrost probe)
Differential for temperature
Pr2
dAH
1.0
alarm (defrost probe)
Temperature alarm delay
Pr2
ddA
15
(defrost probe)
High temperature alarm setting
Pr2
FLU
150
(fan probe)
Low temperature alarm setting
Pr2
FLL
-55
(fan probe)
Differential for temperature
Pr2
FAH
1.0
alarm (fan probe)
Temperature alarm delay (fan
Pr2
FAd
15
probe)
Delay of temperature alarm at
Pr1
dAo
1.3
start-up
Alarm delay at the end of
Pr1
EdA
30
defrost
XM670K_XM679K NL r1 0 2009 01 15.doc
Installatie en gebruikershandleiding
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
0 ÷ 120 (hours)
0 ÷ 255 (min.)
0 ÷ 255 (min.)
rt(0) - it(1) - SEt(2) - dEF(3)
0 ÷ 255 (min.)
0 ÷ 255 (min.)
CoM
n(0) – Y(1)
AOP
0 ÷ 24.0(144)
(hours.10min)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
0 ÷ 100 (100=FPA, 0=FPb)
C-n(0) - O-n(1) - C-y(2) - O-
y(3)
0 ÷ 255 (min.)
[0.0°C ÷ 50.0°C] [0°F ÷ 90°F]
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
0÷15 (min.)
0÷15 (min.)
UAL(0) - rEG(1) - AC(2)
AMi ÷ AMA
nPS
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
OdC
[-25.5°C ÷ 25.5°C] [-45°F ÷
45°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ AMA
CbP
AMi ÷ 100
0 ÷ 255 s
dAY
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - tEr(6)
rE(0) - Ab(1)
[0.0°C ÷ 50.0°C o ALL ÷
150.0°] [0°F ÷ 90°F o ALL ÷
302°F]
[0.0°C ÷ 50.0°C o -55,0°C ÷
ALU]
[0°F ÷ 90°F o -67°F
÷ ALU°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
dSE
0 ÷ 255 (min.)
[0.0°C ÷ 50.0°C o dLL ÷
HES
150.0°] [0°F ÷ 90°F o dLL ÷
302°F]
[0.0°C ÷ 50.0°C o -55,0°C ÷
dLU]
[0°F ÷ 90°F o -67°F ÷
dLU°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
[0.0°C ÷ 50.0°C o FLL ÷
150.0°] [0°F ÷ 90°F o FLL ÷
302°F]
[0.0°C ÷ 50.0°C o -55,0°C ÷
FLU]
[0°F ÷ 90°F o -67°F ÷
FLU°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
0 ÷ 24.0(144)
(hours.10min)
0 ÷ 255 min
XM670K - XM679K
Temperature alarm exclusion
Pr1
dot
15
after door open
Pr2
Sti
nu
Stop regulation interval
Pr2
Std
3
Stop duration
Pr2
oA6
AUS
Sixth relay output configuration
Modulating output configuration
Pr2
oA7
ALr
(if CoM=oA7)
Pr2
Cur
Modulating output configuration
Pr1
cL
Alarm relay polarity
Auxiliary output indipendent
Pr1
iAU
n
from ON/OFF state
Digital
Inputs
Pr1
i1P
cL
Digital input 1 polarity
Pr1
i1F
dor
Digital input 1 configuration
Pr1
d1d
15
Digital input 1 activation delay
Pr1
i2P
cL
Digital input 2 polarity
Pr1
i2F
LiG
Digital input 2 configuration
Pr1
d2d
5
Digital input 2 activation delay
Pr1
i3P
cL
Digital input 3 polarity
Pr1
i3F
ES
Digital input 3 configuration
Pr1
d3d
0
Digital input 3 activation delay
Number of pressure switch
Pr1
15
activation before lock
Compressor and fan status
Pr1
F-C
when open door
Outputs restart after door open
Pr1
rrd
30
alarm
Clock
Pr1
Y
Clock presence
Pr1
Hur
- - -
Current hour
Pr1
Min
- - -
Current minutes
Pr1
- - -
Current day
Pr1
Hd1
nu
First weekly day
Pr1
Hd2
nu
Second weekly day
Pr1
Hd3
nu
Third weekly day
Energy saving cycle start during
Pr1
ILE
0.0
workdays
Energy saving cycle length
Pr1
dLE
0.0
during workdays
Energy saving cycle start during
Pr1
ISE
0.0
holidays
Energy saving cycle length
Pr1
0.0
during holidays
Temperature increasing during
Pr1
0.0
Energy Saving cycle
Pr1
Ld1
nu
Workdays First defrost start
Pr1
Ld2
nu
Workdays Second defrost start
Pr1
Ld3
nu
Workdays Third defrost start
Pr1
Ld4
nu
Workdays Fourth defrost start
Pr1
Ld5
nu
Workdays Fifth defrost start
Pr1
Ld6
nu
Workdays Sixth defrost start
Pr1
Sd1
nu
Holidays First defrost start
Pr1
Sd2
nu
Holidays Second defrost start
Pr1
Sd3
nu
Holidays Third defrost start
Pr1
Sd4
nu
Holidays Fourth defrost start
Pr1
Sd5
nu
Holidays Fifth defrost start
Pr1
Sd6
nu
Holidays Sixth defrost start
1592023011
0 ÷ 255 min
"nu"(0) ÷ 24.0(144)
(hour.10min)
1 ÷ 255 min
CPr(0) - dEF(1) - FAn(2) -
ALr(3) - LiG(4) - AUS(5) -
db(6) - OnF(7)
CPr(0) - dEF(1) - FAn(2) -
ALr(3) - LiG(4) - AUS(5) -
db(6) - OnF(7)
CUr(0) - tEn(1) - PM5(2) -
PM6(3) - oA7(4)
OP(0) - CL(1)
n(0) – Y(1)
OP(0) - CL(1)
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
0 ÷ 255 (min.)
OP(0) - CL(1)
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
0 ÷ 255 (min.)
OP(0) - CL(1)
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
0 ÷ 255 (min.)
0 ÷ 15
no(0) - FAn(1) - CPr(2) - F-
C(3)
0 ÷ 255 (min.)
n(0) – Y(1)
- - -
- - -
Sun(0) - SAt(6)
Sun(0) - SAt(6) - nu(7)
Sun(0) - SAt(6) - nu(7)
Sun(0) - SAt(6) - nu(7)
0 - 23.5(143) (hours.10min)
0 ÷ 24.0(144)
(hours.10min)
0 - 23.5(143) (hours.10min)
0 ÷ 24.0(144)
(hours.10min)
[-30.0°C ÷ 30.0°C] [-54°F ÷
54°F]
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld1 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld2 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld3 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld4 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld5 ÷ 23.5(143) - nu(144)
(hours.10min)
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd1 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd2 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd3 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd4 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd5 ÷ 23.5(143) - nu(144)
(hours.10min)