Maintenance frequency indicator
Fuel oil stock indicator
A4
Display
BP1 Push-button 1
Request: fault code
BP2 Push-button 2
Request: values
After a certain period of operation, the
following information may be displayed:
This means that
maintenance must
be carried out by a
specialist.
If the fitter has
registered his
telephone number,
then this appears,
as well as the
number of the
completed service
contract (accessible
via the fault menu)
To change the telephone number
• Call up the fault menu by pressing
BP1, then keep pressing the button to
scroll through BP1 until the desired
pictogram is displayed.
• Press BP2 to enter a change in the
pictogram: the first figure flashes.
• Select the value (from 0 to 9) by
repeatedly pressing BP1.
• Confirm by pressing BP2.
• Repeat the operation until you reach
the last figure.
After confirming the last figure, the
complete pictogram is displayed for 5
seconds, then the control unit returns to
the operating screen.
To change the contract number
• Call up the fault menu by pressing
BP1, then keep pressing the button to
scroll through until the desired
pictogram «contract number» is
displayed.
• Press BP2 to enter a change in the
pictogram: the first figure flashes.
• Select the value (from 0 to 9) by
repeatedly pressing BP1.
• Confirm by pressing BP2.
• Repeat the operation until you reach
the last figure.
After confirming the last figure, the
complete pictogram is displayed for 5
seconds, then the control unit returns to
the operating screen.
03/2011 - Art. Nr. 4200 1016 4000C
The fuel oil stock indicator can be
accessed:
Nozzle size (value
can be changed)
(0.5 - 1.5)
Pump pressure
(value can be
changed)
(8.0 - 17.0)
Quantity of fuel oil
in the tank (value
can be changed)
Estimating the
quantity of fuel oil
in the tank (value
calculated)
To do this while the burner is
operating:
• Press and hold button BP1 for at least
5 seconds: The nozzle size pictogram
is displayed.
To change the nozzle size:
• Press BP2 to enter a change in the
pictogram: the figure flashes.
• Select the value (nozzle size, in
increments of 0.05 US GAL/h) by
repeatedly pressing button BP1.
• Confirm by pressing BP2.
The screen then displays the pump
pressure.
To change the pump pressure value:
• Press BP2 to enter a change in the
pictogram: the figure flashes.
• Increase the value
(in increments of 0.5 bar) by
repeatedly pressing button BP1.
• Confirm by pressing BP2.
The quantity of fuel oil in the tank is then
shown in the display (fuel oil reserve).
To enter the fuel oil reserve :
• Press BP2 to enter a change in the
pictogram: the figure flashes.
• Enter the value (4 figures from 0 to 9)
by repeatedly pressing BP1.
• Confirm by pressing BP2.
The screen then displays an estimate of
the quantity of fuel oil in the tank. The
value changes over time, depending on
the values entered above and the burner
runtime.
en