Troubleshooting

Fault diagnosis and repair
In the event of a malfunction, first check
that the prerequisites for correct
operation are fulfilled:
1.
Is the system connected to the
power supply?
2.
Is there oil in the tank?
3.
Are all shut-off valves open?
4.
Are all control and safety devices,
such as the boiler thermostat, low-
water detector, limit switch, etc.
adjusted correctly?
If the cause of the malfunction cannot be
ruled out by the checks described
above, check the functions associated
with individual burner parts.
Symbol
No heat request
Burner does not start after
thermostat shutdown.
No malfunction indicated
on the automatic
combustion control unit.
Burner starts at switch-on
for very short period
and then shuts down
Burner starts and then
shuts down after
preventilation
Burner starts and then
shuts down after the
solenoid valves have
opened
Flame extinguishing
during operation
24
Safety components must not be
repaired. They must always be replaced
with parts with the same order number.
Only use original spare parts.
Disconnect the electrical supply
before carrying out any
maintenance or cleaning work.
After any work in the system, check
combustion under normal operating
conditions (doors closed, cover
fitted, etc.). Enter the measurement
values in the boiler room
documentation.
Symbol Fault
Thermostats defective or
incorrectly adjusted
Drop in supply voltage or
power failure.
Control unit malfunction.
The control unit has been
intentionally locked.
Parasitic flame during
preventilation/
pre-ignition phase
No flame signal at end of
safety time
Flame goes out during
operating phase
03/2011 - Art. Nr. 4200 1016 4000C
A4
BP1 Push-button 1
BP2 Push-button 2
Cause
Adjust the thermostats, replace if necessary.
Check the cause of the fall in voltage or the
power failure.
Replace the control unit.
Reset control unit.
Check ignition sparks/adjust or replace
electrode
Check/replace fuel-oil solenoid valve
Check the oil level in the tank.
Top tank up as required.
Open the valves.
Check the oil pressure and the operation of
the pump, coupling, filter, solenoid valve.
Check ignition circuit, electrode adjustment.
Clean/replace electrodes.
Clean/replace flame monitor.
Replace the following items as required:
Ignition electrodes / ignition cables / ignition
transformer / nozzle / pump / solenoid valve /
automatic combustion control unit.
Display
Request: fault code
Request: values
Remedy