Overview
Contents
Overview
Function
Assembly
Commissioning
Service
Important notes
VL 1.40/P/42/55/55P/95 burners are
designed for the combustion of domestic
fuel oil in accordance with national
standards:
AT: ÖNORM C1109: standard or low
sulphur
BE: NBN T52.716: standard or NBN
EN 590: low sulphur
CH: SN 181160-2: domestic fuel oil
and low-sulphur eco fuel oil
DE : DIN 51603-1: standard and low
sulphur.
The design and function of the burners
meet standard EN 267.
Assembly, commissioning and
maintenance must be carried out only by
authorised specialists and all applicable
guidelines and regulations must be
observed.
Burner description
The VL 1.40/P/42/55/55P/95 burner is a
single-stage, fully-automatic
monoblock-type burner. It is suitable for
use, within its range of performance,
with boilers complying with EN 303 or
hot-air generators in line with DIN 4794,
DIN 30697 or EN 621.
Use for any other application requires
the approval of ELCO.
Scope of delivery
The burner packaging also contains:
1
connection clamping flange with
insulation
1
bag containing installation fittings
1
bag containing Technical
Documentation
14
Contents.................................................................. 14
Heating, operating and safety function .................. 16
Setting data, combustion head check ..................... 21
Air regulation,......................................................... 21
Burner adjustment, oil pressure regulation ............. 22
Maintenance ........................................................... 23
The following standards should be
observed in order to ensure safe,
environmentally sound and energy-
efficient operation:
EN 226
Connection of vaporising oil and forced
draught gas burners to the heat
generator
EN 60335-2
Safety of electrical equipment for
domestic use
Place of installation
The burner must not be used in rooms
exposed to aggressive vapours (e.g.
hairspray, tetrachloroethylene or carbon
tetrachloride), large amounts of dust, or
high levels of air humidity (e.g. in laundry
rooms).
If no connection to an air exhaust
system is provided for the air supply,
there must be a supply air inlet
measuring:
DE: up to 50kW: 150 cm
per additional kW: + 2.0 cm
CH: QF [kW] x 6= ...cm
200 cm
Variations may arise as a result of local
regulations.
03/2011 - Art. Nr. 4200 1016 4000C
Page
2
2
2
; but at least
2
.
Declaration of conformity
for forced-draught oil burner
We, the works certified with nr AQF030
F-74106 ANNEMASSE Cedex
declare under our sole responsibility
that the products
VL 1.40/P
VL 1.42
VL 1.55
VL 1.55P
VL 1.95
comply with the following standards:
EN 50165
EN 55014
EN 60335
EN 60555-2
EN 60555-3
EN 267
Belgian royal decree dated 08/01/2004
In accordance with the stipulations of
the following European Directives
98 / 37 /EECMachinery Directive
89 /336 /EECEMC directive
2006 /95 /ECLow Voltage Directive
92 /42 /EECEfficiency directive
these products bear the CE marking.
Annemasse, 27th October 2008
M. SPONZA
We can accept no warranty liability
whatsoever for loss, damage or injury
caused by any of the following:
- Inappropriate use.
- Incorrect assembly or repair by the
customer or any third party, including
the fitting of non-original parts.
Provision of the system and the
operating instructions
The firing system manufacturer must
supply the operator of the system with
operating and maintenance instructions
on or before final delivery. These
instructions should be displayed in a
prominent location at the point of
installation of the heat generator, and
should include the address and
telephone number of the nearest
customer service centre.
Notes for the operator
The system should be inspected by a
specialist at least once a year. It is
advisable to take out a maintenance
contract to guarantee regular servicing.