Specificaties
Netvoeding 3 x 380-500 V AC (FC 302), 3 x 380-480 V AC (FC 301)
FC 301/FC 302
Hoge/normale belasting
Typisch asvermogen [kW]
Behuizing IP 20
Behuizing IP 21
Behuizing IP 55, IP 66
Uitgangsstroom
Continu
(3 x 380-440 V) [A]
Intermitterend (60 s overbelasting)
(3 x 380-440 V) [A]
Continu
(3 x 441-500 V) [A]
Intermitterend (60 s overbelasting)
(3 x 441-500 V) [A]
Continu kVA
(400 V AC) [kVA]
Continu kVA
(460 V AC) [kVA]
Max. ingangsstroom
Continu
(3 x 380-440 V) [A]
Intermitterend (60 s overbelasting)
(3 x 380-440 V ) [A]
Continu
(3 x 441-500 V) [A]
Intermitterend (60 s overbelasting)
(3 x 441-500 V) [A]
10
10
Aanvullende specificaties
IP 21, IP 55, IP 66 max.
kabeldoorsnede
loadsharing) [mm² (AWG)]
IP 21, IP 55, IP 66 max.
kabeldoorsnede
IP 20 max. kabeldoorsnede
motor, rem en loadsharing)
Max. kabeldoorsnede met werkscha-
kelaar [mm² (AWG)]
Geschat vermogensverlies
bij nominale max. belasting [W]
Gewicht, behuizing IP 20 [kg]
Gewicht,
behuizing IP 21, IP 55, IP 66 [kg]
4)
Rendement
Tabel 10.5
70
1)
HO
11
24
38,4
21
33,6
16,6
22
35,2
19
30,4
5)
(net, rem en
16, 10, 16 (6, 8, 6)
2)
10, 10,- (8, 8,-)
5)
(motor) [mm² (AWG)]
2)
5)
(net,
10, 10,- (8, 8,-)
2)
291
4)
MG33AL10 – VLT® is een gedeponeerd handelsmerk van Danfoss
VLT
®
AutomationDrive
Bedieningsinstructies
P11K
P15K
NO
HO
15
15
B3
B3
B1
B1
B1
B1
32
32
35,2
51,2
27
27
29,7
43,2
22,2
22,2
21,5
29
29
31,9
46,4
25
25
27,5
40
16, 10, 16 (6, 8, 6)
10, 10,- (8, 8,-)
10, 10,- (8, 8,-)
16, 10, 10 (6, 8, 8)
392
379
12
12
23
23
0,98
0,98
P18K
NO
HO
NO
18,5
18,5
22,0
B4
B2
B2
37,5
37,5
44
41,3
60
48,4
34
34
40
37,4
54,4
44
26
26
30,5
27,1
31,9
34
34
40
37,4
54,4
44
31
31
36
34,1
49,6
39,6
35,-,-(2,-,-)
35, 25, 25 (2, 4, 4)
35,-,-(2,-,-)
465
444
525
23,5
27
0,98
P22K
HO
NO
22,0
30,0
B4
B2
B2
44
61
70,4
67,1
40
52
64
57,2
30,5
42,3
41,4
40
55
64
60,5
36
47
57,6
51,7
35,-,-(2,-,-)
35, 25, 25 (2, 4, 4)
35,-,-(2,-,-)
547
739
23,5
27
0,98