INSTALLATIoN
Settings
13.1.1 Enter code
The factory-set code is 1 0 0 0.
f Use "+" or "–" to call up the "CodE" menu item.
f
Access level A0 is displayed, alternating with the menu item.
f Press "OK".
f
The code entry field is displayed. The first digit flashes.
f Use "+" or "–" to enter the code 1 0 0 0. After entering each
f
digit, press "OK".
Once the code has been entered correctly, the actual values and
parameters that were previously inaccessible become visible.
13.1.2 Actual values
display
description
I1
Actual room temperature
I2
Relative heating time
(The counter can be reset via param-
eter P5.)
I3
Set charging level for next charge
I4
Actual charging level
13.1.3 Parameters
display
description
P1
Room temperature offset
P2
Time format
P3
Temperature display units
P4
Reset time programs
P5
Reset relative heating time
P6
SL control signal
P7
Type of fan control
P8
Reduce switch-off temperature
P12
Booster heater
P14
Source of set charging level
P15
Source of low tariff enabling
P17
Duty cycle
P18
Fault characteristics
To change the value of a parameter, use the "+" button to call up
the relevant parameter. Press "OK".
As soon as the "Editable parameter" symbol appears, you can
change the parameter value with "+" and "–". Press "OK" to save
the selected value.
If you press the "Menu" button or if no user action is performed
within 10 minutes, the appliance automatically switches to the
standard display. Parameter blocking is reactivated.
P6: SL control signal
options
description
0
SL input deactivated (factory setting):
The fan is controlled via the room temperature controller built
into the appliance.
1
SL input activated:
The fan is controlled via a wall mounted 2-point room tempera-
ture controller.
www.stiebel-eltron.com
All manuals and user guides at all-guides.com
Access
Unit
level
A0
[°C] | [°F]
A0
[h]
A1
[%]
A1
[%]
Access
options
level
A0
±3 °C | ±5 °F
A0
12 h | 24 h
A0
°C | °F
A0
on | off
A0
on | off
A1
0 | 1
A1
0 | 1
A1
100 % | 90 % |
80 % | 70 %
A1
0 | 1
A1
1 | 2 | 3
A1
0 | 1
A1
30 - 80 %
A1
0 | 1
P7: Type of fan control
options
description
0
2-point controller:
The fan is switched on and off by the room temperature controller
built into the appliance, according to heat demand.
1
Proportional controller (factory setting):
The speed of the fan motors is adjusted to the heat demand by the
room temperature controller built into the appliance.
P8: Reducing the switch-off temperature
Using parameter P8, four different charging levels for the electron-
ic charge controller (100 %, 90 %, 80 % or 70 %) can be selected,
in conjunction with the adjustable connected load. The factory
setting is 100 % (no reduction).
If a different setting is selected, a reduced charge level results
(reduced switch-off temperature of the electronic charge control-
ler). See chapter "Specification / Reducing connected load while
maintaining nominal charge duration of 8 hours".
P12: Booster heater (accessory)
options
description
0
If no booster heater is installed in the appliance (factory setting).
1
The booster heater installed in the appliance is activated.
P14: Source of set charging level
options
description
1
For appliances without a weather-compensated charge control
system. The charge volume is controlled via the charge level re-
ducer.
2
The charge control cable is connected to an AC control signal
(factory setting).
3
The charge control cable is connected to a DC control signal.
P15: Source of low tariff enabling
options
description
0
Permanently enabled (factory setting):
The heating elements in the appliance are switched on when the
heating contactor and the electronic charge controller enable
charging.
1
LF hardware signal:
The heating elements in the appliance are not switched on until
the LF from the power supply utility has been enabled and the
electronic charge controller has enabled charging.
P17: Duty cycle
The charge control cable must be connected to an AC control signal
(alternating voltage signal at terminals A1 and A2).
The electronic charge controller in the appliance can be operated
by charge control systems with duty cycles of 80 %, 72 %, 68 %,
40 % and 37 %. The factory setting is designed for duty cycles
of 80 %.
If the appliance is operated with other duty cycles, this parameter
must be adjusted to the appropriate percentage.